MK (E3) 07/2009
page 33/70
Program entry as set-point ramp (example)
W/°C
t/min.
01 02
03
04
-40
-20
0
20
40
60
30 120
180
380
05
Minimum
tolerance
Maximum
tolerance
Operation line 1 = Bedew protection
ON
OFF
t/min.
Operation line 2 (option)
ON
OFF
t/min.
Operation line 3 (option)
ON
OFF
t/min.
Program table corresponding to the diagram above:
Operation lines
Sk
Program
section
No.
Set-point
temp.
W-1
Fan
FAN
Section
time
Time
3 2 1
Target
section
No
No. of
cycles
Cy
Min.
tolerance
Tmin
Max.
tolerance
Tmax
01 -20
****.
00:30:00
Off
Off
Off
1 0 -1999
+9999
02 0
****.
01:30:00
Off
Off
Off
1 0 -5 +5
03 60
****.
01:00:00
Off
Off
Off
1 0 -2 +2
04 60
****.
03:20:00
Off
Off
Off
1 0 -1999
+9999
05 -40
****.
00:00:01
Off
Off
Off
1 0 -1999
+9999
Enter now the values of the above program table into the program table of one of the 25 program places
of the program controller MB1: