8’–24’ POWERFOIL
®
X2.0 & POWERFOIL
®
X2.0PLUS FANS
2
Introduction (cont.)
About this fan
Powerfoil
®
X2.0 specifications
Fan diameter:
8 ft (2.4 m)
10 ft (3 m)
12 ft (3.6 m)
14 ft (4.3 m)
Motor size:
1.0 HP (0.75 kW)
1.0 HP (0.75 kW)
1.0 HP (0.75 kW)
1.5 HP (1.1 kW)
Required supply circuit
size:
10A @ 200–250V 3Φ
10A @ 400–480V 3Φ
20A @ 200–250V 1Φ
10A @ 200–250V 3Φ
10A @ 400–480V 3Φ
20A @ 200–250V 1Φ
10A @ 200–250V 3Φ
10A @ 400–480V 3Φ
20A @ 200–250V 1Φ
15A @ 200–250V 3Φ
10A @ 400–480V 3Φ
30A @ 200–250V 1Φ
Full load current:
3.8A @ 200–250V
1.9A @ 400–480V
3.8A @ 200–250V
1.9A @ 400–480V
3.8A @ 200–250V
1.9A @ 400–480V
5.0A @ 200–250V
2.5A @ 400–480V
Max RPM:
113 RPM
113 RPM
106 RPM
95 RPM
Airfoil length:
37.5 in (1 m)
49.5 in (1.26 m)
61.5 in (1.56 m)
73.5 in (1.87 m)
Suggested distance from
the ceiling
1
:
3 ft (0.9 m)
3 ft (0.9 m)
3 ft (0.9 m)
4 ft (1.2 m)
Fan diameter:
16 ft (4.9 m)
18 ft (5.5 m)
20 ft (6.1 m)
24 ft (7.3 m)
Motor size:
1.5 HP (1.1 kW)
1.5 HP (1.1 kW)
2.0 HP (1.5 kW)
2.0 HP (1.5 kW)
Required supply circuit
size:
15A @ 200–250V 3Φ
10A @ 400–480V 3Φ
30A @ 200–250V 1Φ
15A @ 200–250V 3Φ
10A @ 400–480V 3Φ
30A @ 200–250V 1Φ
15A @ 200–250V 3Φ
10A @ 400–480V 3Φ
30A @ 200–250V 1Φ
15A @ 200–250V 3Φ
10A @ 400–480V 3Φ
30A @ 200–250V 1Φ
Full load current:
5.0A@ 200–250V,
2.5A@ 400–480V
5.0A@ 200–250V,
2.5A@ 400–480V
6.0A@ 200–250V,
3.0A@ 400–480V
6.4A@ 200–250V,
3.0A@ 400–480V
Max RPM:
95 RPM
77 RPM
70 RPM
55 RPM
Airfoil length:
85.5 in (2.17 m)
97.5 in (2.48 m)
109.5 in (2.78 m)
133.5 in (3.39 m)
Suggested distance from
the ceiling
1
:
4 ft (1.2 m)
4 ft (1.2 m)
5 ft (1.5 m)
5 ft (1.5 m)
1. The distance of the fan from the ceiling should be measured from the top of the winglets to the ceiling.
CAUTION: Big Ass Fans requires that the Powerfoil X2.0 fan be supplied from one of the following types of transformers:
575V–600V models: 575V/330V Wye secondary (neutral not utilized)
400V–480V models: 480V/277V Wye secondary (neutral not utilized)
200V–250V models: 208V/120V Wye secondary (neutral not utilized)
240V/120V Delta secondary (Wild/High Phase B)
Integration into any other power distribution scheme may result in improper fan operation or premature hardware failure! See
page 25 for more information.