![BIG ASS FANS BAF-SBL1-1201 Series Installation Manual Download Page 12](http://html1.mh-extra.com/html/big-ass-fans/baf-sbl1-1201-series/baf-sbl1-1201-series_installation-manual_2749840012.webp)
WWW.BIGASSFANS.COM © 2019 DELTA T LLC
10
POWER WIRING
Refer to the input voltage rating marked on the fixture, and then wire according to
the diagram and table below.
Note: The dimming cable is optional.
Supply voltage
Fixture’s L1 (black)
connects to
Fixture’s L2 (white)
connects to
Low voltage fixture
(120–277 V ± 15%)
120 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
H (black)
N (white)
208 VAC, 3 Ф derived from 3 Ф,
208/120 V panel
L1 (black), L2 (red), or L3
(blue)
L2 (red), L3 (blue), or L1
(black)
240 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
L1 (black)
L2 (red)
240 VAC, 1 Ф derived from 3 Ф,
240/120 V panel, B phase wild
L1 (black), L2 (orange), or
L3 (blue)
L2 (orange), L3 (blue), or
L1 (black)
All
277 VAC, 1 Ф derived from 3 Ф,
480/277 V panel
L1 (brown), L2 (orange), or
L3 (yellow)
N (white)
(347–480 V ± 15%)
347 VAC, 1 Ф derived from 3 Ф,
600/347 V panel
L1 (red), L2 (black), or L3
(blue)
N (white)
480 VAC, 3 Ф derived from 3 Ф,
480/277 V panel
L1 (brown), L2 (orange), or
L3 (yellow)
L2 (orange), L3 (yellow),
or L1 (brown)
480 VAC, 1 Ф derived from 3 Ф,
480 V panel, corner ground
L1 (brown) or L3 (yellow)
L2/Grounded conductor
(white or gray)
GROUND
(GREEN IN US/CA/MX; GREEN
W/YELLOW OUTSIDE US/CA/MX)
L1
(BLACK IN US/CA/MX; BROWN
OUTSIDE US/CA/MX)
L2
(WHITE IN US/CA/MX; BLUE
OUTSIDE US/CA/MX)
DIM-
(GRAY)
DIM+
(VIOLET)
FIXTURE
GROUND
L1
L2
POWER
DIM-
(GRAY)
DIM+
(VIOLET)
DIMMING
(1–10 VDC)