8’ - 24’ POWERFOIL® X
WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED
3
WWW.BIGASSFANS.COM ©2011 DELTA T CORP. DBA BIG ASS FAN CO. ALL RIGHTS RESERVED
8’ - 24’ POWERFOIL® X
About this Fan (cont.)
Powerfoil® X Specifications (with PowerfoilPlus Winglets)
FAN DIAMETER:
10 ft (3 m)
12 ft (3.6 m)
14 ft (4.3 m)
16 ft (4.9 m)
AIR DISP. @ MAX SPEED:
100,871 cfm (47,606 l/s) 132,536 cfm (62,550 l/s) 144,556 cfm (68,223 l/s) 184,944 cfm (87,284 l/s)
MOTOR SIZE:
1.0 HP (.75 kW)
1.5 HP (1.1 kW)
1.5 HP (1.1 kW)
1.5 HP (1.1 kW)
REQUIRED SUPPLY
CIRCUIT SIZE:
10A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
FULL LOAD CURRENT:
3.4A @ 200-250V,
1.7A @ 400-480V
5.6A @ 200-250V,
2.8A @ 400-480V
5.6A @ 200-250V,
2.8A @ 400-480V
5.6A @ 200-250V,
2.8A @ 400-480V
MAX RPM:
84 RPM
72 RPM
63 RPM
56 RPM
AIRFOIL LENGTH:
49.5 in (1.26 m)
61.5 in (1.56 m)
73.5 in (1.87 m)
85.5 in (2.17 m)
FAN WEIGHT*:
296 lbs (134 kg)
312 lbs (141 kg)
329 lbs (149 kg)
345 lbs (156 kg)
SUGGESTED DISTANCE
FROM CEILING**:
7 ft (2.1 m)
7 ft (2.1 m)
7 ft (2.1 m)
7 ft (2.1 m)
(cont.)
FAN DIAMETER:
18 ft (5.5 m)
20 ft (6.1 m)
24 ft (7.3 m)
AIR DISP. @ MAX SPEED:
210,046 cfm (99,111 l/s)
235,148 cfm
(110,978 l/s)
368,516 cfm
(173,920 l/s)
MOTOR SIZE:
1.5 HP (1.1 kW)
2.0 HP (1.5 kW)
2.0 HP (1.5 kW)
REQUIRED SUPPLY
CIRCUIT SIZE:
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
15A @ 200-250V 3Φ
10A @ 400-480V 3Φ
30A @ 200-250V 1Φ
FULL LOAD CURRENT:
5.6A @ 200-250V,
2.8A @ 400-480V
6.4A @ 200-250V,
3.2A @ 400-480V
6.4A @ 200-250V,
3.2A @400-480V
MAX RPM:
47 RPM
46 RPM
39 RPM
AIRFOIL LENGTH:
97.5 in (2.48 m)
109.5 in (2.78 m)
133.5 in (3.39 m)
FAN WEIGHT*:
361 lbs (164 kg)
413 lbs (187 kg)
446 lbs (202 kg)
SUGGESTED DISTANCE
FROM CEILING**:
7 ft (2.1 m)
7 ft (2.1 m)
7 ft (2.1 m)
*Weight does not include mounting yokes or extension tube. Add 36 lbs for standard mount kit with 1 ft extension, and 4 lbs for every
additional foot of extension length. Add 5 lbs more for large upper yoke.
**The distance of the fan from the ceiling should be measured from the top of the winglet to the ceiling.
CAUTION—Big Ass Fans requires that the Powerfoil X fan be supplied from one of the following types of
transformers:
400-480V models: 480V / 277V Wye Secondary (Neutral not utilized)
200-250V models: 208V / 120V Wye Secondary (Neutral not utilized)
240V / 120V Delta Secondary (Wild / High Phase B)
Integration into any other power distribution scheme may result in improper fan operation or premature hardware failure! See
p. 24 for more information.
Summary of Contents for 8'-24' Powerfoil X
Page 1: ...8 24 Powerfoil X INSTALLATION GUIDE...
Page 55: ......
Page 63: ......
Page 65: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ...170511 REV B 2425 Merchant Street Lexington KY 40511 1 877 BIG FANS 1001120101...