21
Installation, Operation and Maintenance Manual
MAN 707 Rev. 3
Section 3: Operation and Use
Operation and Use
March 2022
3.6
Calibration of the Operation Time
For actuator models equipped with control system, it’s possible to regulate the speed
of actuator operations. The calibration of the operation time is made by Biffi Italia s.r.l.
according to customer requirements and to technical data sheet included in technical
documentation. If necessary, it’s possible to modify or reset the operating time through
the flow regulating valve (optional) placed on inlet of hydraulic cylinder (refer to specific
technical documentation furnished with actuator's scope of supply).
Figure 19
Adjustment of operating time by flow-regulator valve
Torque 30 Nm
Torque 5 Nm
Technical features:
Max. adjusted flow
(L/min.)
10
Max. working pressure
(bar)
250
Fluid viscosity range
(cSt)
5 - 750
Fluid temperature range
(°C)
-45 +60
Mass
(Kg)
0.70
Hydraulic fluid: mineral oils
Recommended filtration: 19/15 ISD 4466 (25
µ
absolutes)
Seals in MFQ (Fluoro-silicone)
POS
QTY
Denomination
Material
Type or Drawing
8
1
OR + 2BK (included in cartridge pos. 2)
MFQ-70Sh+PTFE
OR2-013 + 2BK
7
1
Handwheel
11S (2011)
29.102.378
6
4
Screw
A4-70
VTCEI M5x45 UNI 5931
5
2
O-ring
MFQ -70Sh
OR 5-612
4
1
Screw
A4-70
M5x5 UNI 5923
3
1
O-ring (included in cartridge pos. 2)
MFQ-70Sh
OR 2-116
2
1
Cartridge
AISI 316
FT 2267/2-14-FQSV
1
1
Body
AISI 316
49.144.031
Table 4.
To carry out the adjustment, operate the handwheel (turn the handwheel clockwise to
increase the operating time or turn the handwheel counterclockwise to decrease the
operation time).