25
Installation, Operation and Maintenance Manual
MAN 707 Rev. 3
Section 5: Maintenance
Maintenance
March 2022
AGIP MU/EP/2
To be used in standard
temperature conditions:
(-30 °C/+85 °C)
NGLI consistency:
2
Worked penetration:
280 dmm
ASTM dropping point:
185 °C
Base oil viscosity at 40 °C: 160 mm²/s
ISO Classification:
L-X-BCHB 2
DIN 51 825:
KP2K – 20
Equivalent to:
ESSO BEACON EP2
BP GREASE LTX2
SHELL ALVANIA GREASE R2
ARAL ARALUB HL2
CHEVRON DURALITH GREASE EP2
CHEVRON SPHEEROL AP2
TEXACO MULTIFAK EP2
MOBILPLEX 47
PETROMIN GREASE EP2
AEROSHELL GREASE 7 or equivalent
To be used in
low temperature
conditions:
(-60 °C/+65 °C)
Color:
Buff
Physical state:
Semi-solid at ambient
temperature
Odor:
Slight
Density:
966 kg/m³ at 15 °C
Flash point:
>215 °C (COC) (Based on
synthetic oil)
Dropping point:
260 °C (ASTM D-566)
Product code:
001A0065
Infosafe No.:
ACISO GB/eng/C
Table 6.
5.2
Extraordinary Maintenance
If there are leaks in the hydraulic cylinder, or a malfunction in the mechanical components,
or in case of scheduled preventive maintenance, the actuator must be disassembled and
seals must be replaced with reference to the following general sectional drawing and
adopting the following procedures.
5.2.1
Replacement of Cylinder Seals
(refer to Figure 22, Section 7.2)
NOTICE
Before carrying out any maintenance operation, it is necessary to close the hydraulic feed
line and exhaust the pressure from the actuator cylinder and from the control unit to
ensure safety of maintenance staff.
!
WARNING
If the actuator can be operated, it is essential to take it to fail-safe position with the spring
totally extended.
HLAS-C does not need lubrication during its life. However, it’s possible to utilize the
following grease during special maintenance operations, for example, to lubricate the
spring's surface inside spring cartridge.