June 2021
Installation, Operation and Maintenance Manual
MAN712 Rev. 9
Section 6: Configuration Parameters
Configuration Parameters
52
6.2
Table of Digital Outputs Functions
Table 7.
DO FUNCTION
DESCRIPTION (*)
DO AVAILABILITY (*)
OFF
无
It forces the Relay to have a not active associated function.
All
SOV C.
(SOV CONTROL)
安全动作已执行
It is active when the Safety Action starts, and it is cleared when the
Operating Mode is set to VC or VC+ACQ.
This function can be used both for monitoring the safety action and for using
DO1 or DO2 as SOVs Control Outputs (connected to the SOVs). In any case
at least one between SVC1, SVC2, RL1 and RL2 must be enabled.
If DO1 or DO2 are used as SOVs Control Outputs (connected to the SOVs), it
is necessary to follow the “Restore the Valve Control” procedure
(see Section 11) to correctly clear them.
DO1, DO2
ARMED
阀门控制模式
It is active when the ELBS-20 is in VC or VC+ACQ operating mode
(see Section 5.1.1).
All
ALARM
系统报警
It is active when at least one alarm is active (see Section 6.4).
All
ACQ.
(ACQUISITION)
数据采集模式
It is active when the ELBS-20 is in ACQ or VC+ACQ operating mode
(see Section 5.1.1).
All
WARN.
(WARNING)
系统警告
It is active when at least one warning is active (see Section 6.4).
All
S. ACT
(Safety action)
安全动作激活
It is active when the Safety Action it is considered as “active”
(see Section 5.1.2.7).
DO1, DO2
V.E.KO
(External Power
Supply KO)
外部供电异常
It active when at least one of the following warnings is active: “External
Power Supply Default” or “External Power Supply Auxiliary”
(see Section 6.4).
All
V.B.KO
(Battery Pack Power
Supply KO)
电池供电异常
It is active when at least one of the following warnings is active: “Battery
Pack Default” or “Battery Pack Auxiliary” (see Section 6.4).
All
HEATER
低温启动加热器
The ELBS-20 use this DO for driving an external HEATER connected on the
DO7.
-30 °C is the threshold for activating the HEATER.
-28 °C is the threshold for de-activating the HEATER.
DO7
B.MNT
(Battery Maintenance
Required)
电池维护要求
It is active when the “Battery Maintenance Required” warning is active.
All
S.A DONE
(Safety Action Done)
阀门动作结束
It becomes active at the end of the execution of the Safety Action, when the
ELBS-20 considers the Safety Action as no more “active”
(see Section 5.1.2.7).
It is cleared when the Operating Mode is set to VC or VC+ACQ.
All
SVC KO
电磁阀异常
It is active when at least one of the following warnings is active:
“SVC1” or “SVC2” (see Section 6.4).
All
RL KO
电磁阀异常
It is active when at least one of the following warnings is active:
“RL1” or “RL2” (see Section 6.4).
All
EVENT 2
事件类型
2
It is active when “EVENT2” occurs or, if the Operating Mode is SLOW, the
Pressure value is lower than the “LP Limit” parameter.
Once activated, it’s cleared when the Pressure value is equal or higher than
the “LP Limit” parameter or after a power cycle.
All (**)
EVENT 4
事件类型
4
It is active when “EVENT4” occurs or, if the Operating Mode is SLOW, the
Pressure value is higher than the “HP Limit” parameter.
Once activated, it’s cleared when the Pressure value is equal or lower than
the “HP Limit” parameter or after a power cycle.
All (**)
EVENT 6
事件类型
6
It is active when “EVENT6” occurs.
Once activated, it’s cleared when the Operating Mode is reset to VC or
VC+ACQ (the ELBS20 is ARMED) or after a power cycle
All (**)
NOTES:
(*):
DO7 works only when the External Power Supply is applied (NO contact is always Open and NC
contact is always Closed).
(**):
The “EVENT2”, “EVENT4” and “EVENT6” functions are available starting from Process Card FW
2.00.06 and Interfaces Card FW 2.00.11.