PD800W Meter Probe (DEG Position ONLY)
DEG –
Phase angle measurement in degrees for use on Secondary, URD and
Overhead. Direct contact from 240V to 69kV
(including capacitive test points).
Non-contact from 69kV to 800kV.
T – Tests
basic meter function and displays the internal 9V battery voltage.
0 degree light -
indicates an in-phase condition relative to send unit
120 degree light -
indicates out-of-phase condition of 120 degrees.
240 degree light -
indicates an out-of-phase condition of 240 degrees.
Yellow “DY” -
blinking light indicates a Delta/Wye transformation (30 degree or
greater phase shift) in conjunction with one of the other three phase indicator
lights.
NOTE1: A reading less than 07.0 in the test position indicates low battery.
Replaceable 9V battery is located behind the live line tool attachment threaded
into the meter housing just below the battery label on the display side of the
meter.
WARNING
Unit shall be tested before and after each use on a known voltage source.
Failure to do so could result in false negative indications.