5
Design and Function
WARNING
Limit Mark
-see “Product Safety Information”, item 3, page 4.
The Phasing Ranger 2 is designed to operate in conjunction with the Cordless
PD800W Meter Probe only. The unit consists of two main devices; a Send Unit
and a Receive Unit. The Send Unit plugs into a standard 115V AC wall outlet
and a land line telephone outlet via a standard telephone cord (provided). The
Receive Unit is power by rechargeable batteries and a cell phone via an audio
cable or the more convenient Bluetooth Connection using you Bluetooth
enable phone. There is an ac power or dc power cable to charge the battery
when it is low for either in a building or out on the road in a truck. The Receive
Unit talks directly to the Meter Probe to provide the correct phase angle. The
Phasing Ranger 2 is useable from 120/208 V to 800kV at a tested distance of
1000 miles.
Each unit has an On-Off switch, a red Power light, a red charging light (Field
unit only), and a white Data light. A Solid red power light indicates power
supply voltage is good, a Blinking red power light indicates power supply
voltage is low, and No red power light indicates too low or no power supply
voltage. A solid red charging light indicates the unit is plugged in to a good
charging source ad charging the batteries. No Red charging light indicates there
is no charging voltage present. A Solid white light indicates satellite data and
phase angle data is good, a slow blinking (1 pulse per second) white light
indicates satellite data is good but phase angle data is not present, and No
white light indicates data is not available.
Summary of Contents for Phasing Ranger 2
Page 16: ...16 ...