2.3
Hanging the unit up
2.3.1 Determining the location of the unit
• Make sure that the structure from which the unit is about
to be suspended can bear at least 4 times the weight of the
unit. The unit’s weight is indicated on its type plate.
• Note the following dimensions:
- The unit must be at least as wide as the door opening
(dimension b).
- Position the unit as near to the doorway as possible.
- Position the unit as close to the top of the door as pos-
sible.
Warning:
w
The minimum installation height (dimension
h) is 1.8 m.
-
If the unit is mounted against the ceiling:
Make
sure that air can enter the unit freely above the unit.
Warning:
w
The top of the unit may get hot. The unit
should be placed with at least 25 mm ceiling
clearance (dimension x).
See also:
2.3.2 Attaching the wall consoles (accessory)
Attach the wall consoles in accordance with the instructions
supplied.