I
NSTALLATION
C
OMFORT
C
IRCLE
12
General instructions
Some parts of this section are applicable only to certain mod-
els. Where this is the case, it will be indicated. If no specific
model is referred to, the description applies to all models.
Note:
n
Make sure you perform all installation operations that are
required for your unit.
Check the type plate. Refer to section 1.3.4 if you are not
sure about the model or type of your unit.
Note:
n
Protect the unit from damage and ingress of dust, cement,
etc. throughout the installation. You can, for instance, use
the packaging for protection.
2.4
Mounting the unit
2.4.1 Positioning the unit
•
Make sure that the structure from which the unit is about
to be suspended can hold the weight of the unit. The
weight is specified on the type plate (see section 1.3.4).
•
Ensure the following:
-
Position the unit between the ceiling profiles.
-
Give heed to the unit’s orientation in the room (it is
possible to adapt the discharge pattern to the room –
see section 2.12).
-
The maximum mounting height for the unit is 3.5 m. (,
measured from floor to ceiling).
Caution:
c
Provide for an inspection hatch in the ceiling if the Com-
fort Circle is not fitted in a suspended ceiling.
Warning:
w
The
minimum
mounting height is 2.0 m.
Note:
n
Mounting the unit above the maximum height may affect
the proper working of the unit.