UPSI-2406DPx
Revision 1-5
17
ENVIRONMENTAL CONDITIONS
Ambient temperature (operation)
DP1: 0…+50° C / DP2: -20… +65° C / DP3: -20… +55° C
Ambient temperature (start up without load) DP2: -30° C / DP3: -20° C
Ambient temperature
(storage / transport)
DP1: -20…+50° C / DP2: -30…+65° C / DP3: -30…+55° C
Max. permitted humidity
≤95 % (at +25° C, no dew)
Operating altitude
≤4000 m
Climate class
3k3 (EN 60721)
Degree of pollution
2
Overvoltage category
EN 61010-1
EN 61010-2-201
I
I
Indoor / Outdoor use
Yes / Yes (in housing)
STANDARDS
Safety extra-low voltage
IEC 61010-1 (SELV)
IEC 61010-2-201
APPROVALS (valid only for UPSI-2406DP1 and UPSI-2406DP2)
UL
ETL, UL61010-1
ETL, UL61010-2-201
CSA
CSA C22.2 61010-1-12
CSA C22.2 61010-2-201
CB Scheme
IEC 61010-1
IEC 61010-2-201