UPSI-2406DPx
Revision 1-5
15
CONNECTION DATA – RELAY
Connection labeling
RL
Switch contact (potential free)
Relay
Status (configurable)
Power Fail Alarm
Switching voltage
24 V DC / 125 V AC
Current carrying capacity
1 A (DC) / 0.5 A (AC)
State - signal assignment
NO (Normally Open) / NC (Normally Closed) –
configurable via Software
Connection method
Lockable connector
Conductor cross-section solid
0.205 mm² … 1.3 mm² (24 … 16 AWG)
Conductor cross-section flexible
0.205 mm² … 1.3 mm² (24 … 16 AWG)
Conductor cross-section with ferrule
0.205 mm² … 1.3 mm² (24 … 16 AWG)
Stripping length
7 mm … 9 mm
DATA INTERFACE – USB
Interface designation
USB
Numbers of interfaces
1
Connection method
USB type B (female)
Locking
No
Transmission physics
USB 2.0
Topology
Point-to-point
Protocol
VCOM, HID
Transmission length
≤3 m
Access time
<1 s
Chipset
NXP
Electrical isolation
No