CI-1 Front 

Front Panel Information 

The CI-1 has three switches on the front panel and an internal (local) sounder, audible through the panel. 

 

 

 

Local Sounder 

The local sounder commence whenever any alarm input receives an external signal from the fire 
detection equipment, control and indicating equipment (CIE) or equivalent. 

It will also commence when any fault is detected. The sounder will continue until the alarm or fault is 
reset. 

 

Local Sounder Silence Switch 

If the local sounder is operating, this switch may be used to silence it. The alarm or fault condition that 
caused the sounder to operate is unaffected by operating this switch. If a new alarm or fault is detected, 
the sounder will restart. Press and hold the switch for two seconds to operate. 

 

System Test Switch 

This switch will initiate a test sequence on the LSI-16(e). All indicators in use on the LSI-16(e) will light 
briefly and the sounder in the CI-1 will sound briefly, thus confirming that essential annunciators are 
functional. Press and hold the switch for two seconds to initiate the test sequence. 

 

System Fault Reset Switch 

A System Fault denotes that the LSI-16(e) cannot guarantee correct operation of the Vocia system in an 
emergency mode. It is indicated on the LSI-16(e) and by the sounder in the CI-1. A system fault can only 
be cleared by operating the System Fault Reset switch.  

Note

: when the LSI-16(e) is powered up, the System Fault will be operational until the System Fault 

Reset switch is pressed. Press and hold the switch for two seconds to reset a System Fault. 

Summary of Contents for Vocia CI-1

Page 1: ...CI 1 OPERATION MANUAL May 2019 585 0279 90B ...

Page 2: ...CI 1 Product Description The CI 1 Control Interface is a companion product to the Vocia LSI 16 Life Safety Interface It facilitates necessary connections to the LSI 16 LSI 16e to meet EN 54 16 standards ...

Page 3: ...r alarm condition This is normal operation For correct fault free operation inputs and outputs must be connected to the LSI 16 e and CI 1 or external equipment as detailed in this manual Installation Install the unit away from heat sources such as vents and radiators and in rooms with adequate ventilation Ensure that air can circulate freely behind beside and above the unit Do not exceed the maxim...

Page 4: ...ted the sounder will restart Press and hold the switch for two seconds to operate System Test Switch This switch will initiate a test sequence on the LSI 16 e All indicators in use on the LSI 16 e will light briefly and the sounder in the CI 1 will sound briefly thus confirming that essential annunciators are functional Press and hold the switch for two seconds to initiate the test sequence System...

Page 5: ...ncy message is playing A pulsed output 1 25Hz indicates that an alarm is active but emergency messages have been silenced The General Fault Output is provided to signal to the fire detection system that there is a fault in the Vocia system that could affect delivery of an emergency message The Voice Alarm Active and General Fault outputs pull low to ground when active The outputs are monitored by ...

Page 6: ... need an external pull up Connections to LSI 16 e These circuits are provided on Four five position plug in barrier strip connections One three position plug in barrier strip connector One DC barrel jack Circuit connections may be made by directly connecting pin for pin to the vertically adjacent connector Short interlinking cables are provided with the CI 1 for this purpose Refer to the LSI 16 e ...

Reviews: