background image

 

CI-1 Setup and Installation 

Setup and Use 

The CI-1 interfaces directly to LSI-16(e) devices and external equipment.  

 

NOTE: To operate correctly, the CI-1 requires an accompanying LSI-16(e) plus connections to external 
components and devices as described in this manual. 

 

The CI-1 should be mounted in close proximity to the accompanying LSI-16(e). 

For EN 54-16 compliance, refer to the Vocia VACIE Reference Guide which details mandatory installation 
requirements. 

 

Incorrect configuration, removal, or non-installation of some system elements may result in the LSI-16(e) 
or CI-1 reporting a fault or alarm condition. This is normal operation. For correct, fault-free operation, 
inputs and outputs must be connected to the LSI-16(e) and CI-1 or external equipment as detailed in this 
manual.  

 

Installation 

Install the unit away from heat sources, such as vents and radiators, and in rooms with adequate 
ventilation. Ensure that air can circulate freely behind, beside, and above the unit. Do not exceed the 
maximum ambient operating temperature of 32° - 108° F (0° - 42°C). Be aware of conditions in an 
enclosed rack that may cause the temperature to exceed ambient room conditions. 

The unit requires one 1.75 inch (44.45 mm) high and 19-inch-wide rack space with 10 inch (254 mm) 
depth. Mounting the unit using four screws with washers will prevent marring of the front panel. PVC or 
nylon washers are appropriate.

Summary of Contents for Vocia CI-1

Page 1: ...CI 1 OPERATION MANUAL May 2019 585 0279 90B ...

Page 2: ...CI 1 Product Description The CI 1 Control Interface is a companion product to the Vocia LSI 16 Life Safety Interface It facilitates necessary connections to the LSI 16 LSI 16e to meet EN 54 16 standards ...

Page 3: ...r alarm condition This is normal operation For correct fault free operation inputs and outputs must be connected to the LSI 16 e and CI 1 or external equipment as detailed in this manual Installation Install the unit away from heat sources such as vents and radiators and in rooms with adequate ventilation Ensure that air can circulate freely behind beside and above the unit Do not exceed the maxim...

Page 4: ...ted the sounder will restart Press and hold the switch for two seconds to operate System Test Switch This switch will initiate a test sequence on the LSI 16 e All indicators in use on the LSI 16 e will light briefly and the sounder in the CI 1 will sound briefly thus confirming that essential annunciators are functional Press and hold the switch for two seconds to initiate the test sequence System...

Page 5: ...ncy message is playing A pulsed output 1 25Hz indicates that an alarm is active but emergency messages have been silenced The General Fault Output is provided to signal to the fire detection system that there is a fault in the Vocia system that could affect delivery of an emergency message The Voice Alarm Active and General Fault outputs pull low to ground when active The outputs are monitored by ...

Page 6: ... need an external pull up Connections to LSI 16 e These circuits are provided on Four five position plug in barrier strip connections One three position plug in barrier strip connector One DC barrel jack Circuit connections may be made by directly connecting pin for pin to the vertically adjacent connector Short interlinking cables are provided with the CI 1 for this purpose Refer to the LSI 16 e ...

Reviews: