Operation Control Features

FIELD-ADJUSTABLE

PRESSURE & ALARM SETPOINTS

PFS - (Primary Fan Speed) Adjusts primary fan speed to
set desired pressure. CW (Clockwise) to decrease.

Factory setpoint:

0.25"

Normal range of adjustment:

0.10" to 0.40"

ASP - (Alarm Setpoint) Adjusts alarm setpoint to activate
alarm at desired pressure.  CW (Clockwise) to decrease.

Factory setpoint:

0.15"

Normal range of adjustment:

0.05" to 0.25"

FIELD-ADJUSTABLE

SECONDARY FAN & ALARM DELAYS

SFD - (Secondary Fan Delay) adjusts time delay cycle to
prohibit secondary fan from engaging when pressure falls
below alarm setpoint.

Factory setpoint:

0 seconds

Normal range of adjustment:

0-35 seconds

ASD - (Alarm Signal Delay) adjusts time delay cycle to
prohibit alarm relay from deenergizing when pressure falls
below alarm setpoint.

Factory setpoint:

15 seconds

Normal range of adjustment:

0-35 seconds

Notes:   Time delay cycles reset automatically if "safe"

building pressure is restored before cycles end.

All controls permit real-time adjustment.

Emergency Remote Control

OPTIONAL USER INPUTS

ESD - (Emergency Shutdown) When VFD Interface Board
jumper is installed, unit allows user to remotely disengage
primary and secondary fans, regardless of primary and
secondary fan control switch positions.

Typical input devices:  emergency shutdown switches, fire
extinguishing or alarm systems and stack mounted
combustible gas or hydrogen sulfide sensors.

ECO - (Emergency Control Override) When VFD Interface
Board jumper is installed, unit allows user to remotely
engage primary and secondary fans, regardless of primary
and secondary fan control switch positions.

Typical input devices:  control room mounted combustible
gas, hydrogen sulfide, or oxygen deficiency sensors.

OPTIONAL WIRING METHODS

HW - (Hard Wiring) Selection of this option requires the
use of conduit, seals and wiring approved for the location.

IS - (Intrinsically Safe) Selection of this option allows use
of intrinsically safe cabling approved for the location.

NOTE: Loops are self-powered 5 VDC 20 ma signals,

regardless of wiring method selection.  Signals
must be maintained independently by normally
closed switches to prevent shutdown or override.

PRIORITY SELECTION SWITCH

In cases where both optional inputs are utilized, VFD
Interface Board jumper allows user to select the preferred
action (shutdown or override) in the unlikely event of
simultaneous loss of signal.  When VFD Interface Board
priority (PTY) jumper is installed, priority is given to the
Emergency Control Override function.

See rear cover for ESD & ECO input ordering information.

VFD Interface Card

Explosion Proof

Control Enclosure Door

Electrical Field Wiring Diagrams

Transducer

Interface

Cable Header

ESD & ECO

Interface

Cable Header

Microprocessor

Door Card

Interface

Cable Header

ECO Enable Pin

ESD Enable Pin

Priority Select Pin

Alarm Relay

20 Amp T1 & T2

Output Fuses

Sec. Fan Relay

Alarm Relay

Terminals

Explosion Proof

Control Enclosure

Variable

Frequency Drive

VFD Interface

Card

Control Operators

& Indicators

Operator Wiring

Cable Interface Card

VFD

Interface

Cable Header

Alarm Signal

Delay Timer

(ASD)

Primary Fan

Speed Control

(PFS)

Alarm Setpoint

Control

(ASP)

Secondary Fan

Delay Timer

(SFD)

Transformer

1 Amp L1

Input Fuse

220 VAC Power

In (Gnd, L1 & L2)

Secondary Motor

Output (T1 & T2)

Intrinsically

Safe Version

Optional ESD & ECO Inputs

1

2

3

4

ESD Out

ESD In

ECO Out

ECO In

Hard Wire

Version

AC Power & Primary Fan

VFD Controller Terminal - TM2

L2

(hot)

L1

(hot)

T1

T2 T3

Unit Power In

208-240 VAC

Power Out 

 

to DS-1

Primary Motor

Disconnect Switch

Alarm Relay & Secondary Fan

VFD Interface Card Terminal - P4

NC

C

NO

T1
T2

Power out

to DS-2

Secondary

Motor

Disconnect

Switch

Alarm Relay

Contacts

15 amps @ 120 VAC

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Normally

Closed

Contacts

Summary of Contents for RDP-12

Page 1: ... a local disconnect switch connected ahead of building power or connected to a separate power source The unit is started by closing the building door and placing the secondary fan switch in the automatic position and the primary fan switch in the on position The primary fan then engages to regulate air flow and maintainasafepressure Whenthedoorisopened pressure will fall below the alarm setpoint T...

Page 2: ...tedbuilding Inaddition thehousingcanbesupplied with an optional emergency remote control junction box for ECO or ESD IS barrier applications Theblowerhousingisfittedwithprimaryandsecondary fans mounted in a compact in line arrangement with the secondary fan mounted directly behind the primary fan Each motor is connected with approved MI mineral insulated cabletoseparatedisconnectswitchesmounted ex...

Page 3: ... HW Hard Wiring Selection of this option requires the use of conduit seals and wiring approved for the location IS Intrinsically Safe Selection of this option allows use of intrinsically safe cabling approved for the location NOTE Loops are self powered 5 VDC 20 ma signals regardless of wiring method selection Signals must be maintained independently by normally closedswitchestopreventshutdownorov...

Page 4: ...GDM 100 Hydrogen Sulfide Monitor HGDS 100 Hydrogen Sulfide Sensor OGDM 100 Oxygen Deficiency Monitor OGDS 100 Oxygen Deficiency Sensor GDPS 100 24 VDC Monitor Power Supply GDSB 1216 Sensor Stack Mount Bracket REMOTE MOUNT DISCHARGE COMPONENTS ADGA 12 Adj Discharge Grill Assembly DE 12 Discharge Extension DN 12 Discharge Ninety DCF 12 Discharge Curb Flange 10 75 6 5 9 5 18 Control Enclosure Front V...

Reviews: