1) FOREWORD

The AXXEDO Q-BO SA residential access control kit lets you 

manage access control and start services in condominium 

applications. 

It includes a 125kHz proximity reader, a backlit 12 capacitive 

key keyboard, on-board memory of 400 user codes (output 

activation codes), 2 activation outputs (entrance opening, 

stairwell lights on) with programmable timer, built-in room 

light sensor for automatic lights on and high efficiency buzzer.

WARNING: Keep the anti-tamper Allen key provided in 

the kit.

2) TECHNICAL SPECIFICATIONS

Power supply

from 12 to 24Vac/Vdc ±15%

Operating tempe-

rature range

-10 / +40∞C

OUT1, OUT2 

outputs

MAX 2A 30Vdc

Idle absorption

40mA @ 12Vdc, 20mA @ 24Vdc

Peak absorption

120mA @ 12Vdc, 60mA @ 24Vdc

Proximity 

reader

125kHz

Dimensions

FIg.A

User codes

MAX 400

Master code

1

IP rating

IP55

When two AXXEDO Q.BO SA are installed, keep then at 

least 1 metre apart.

3) INSTALLATION (Fig.B points 1-6)

Note: drill a hole in the centre of the base big enough for 

wires to pass as illustrated.

4) TERMINAL BOARD WIRING FIG.C 

WARNINGS - When performing wiring and installation, refer 

to the standards in force and, whatever the case, apply good 

practice principles.

Wires carrying different voltages must be kept physically 

separate from each other, or they must be suitably insulated 

with at least 1mm of additional insulation. 

Wires must be secured with additional fastening near the 

terminals, using devices such as cable clamps.

TERMINAL

DESCRIPTION

PWR

12-24Vac/Vdc  ±15% power

OUT1

Entrance control  relay output

OUT2

Stairwell light control relay output

4.1) POWER

The AXXEDO Q.BO SA peripheral can be powered with voltage 

from 12 to 24Vac/Vdc ±15% through PWR terminals.

4.2) OUTPUTS

The reader has 2 relay outputs (2A 30Vdc) with normally open 

contact (NA) and programmable timer, identified with: 

OUT1 -> entrance opening control 

OUT2 -> stairwell lights on control 

Each relay output timer can be set using the reader program-

ming function.

The stairwell lights on control - OUT 2 - can be activating by 

holding down key E on the reader keyboard; this function can 

also be turned on/off using dip switch 2.

WARNING: Use suppression filters to protect the device 

from disturbances generated by inductive loads such as 

relay coils, electro-lock coils and VDR to protect the reader 

from transistors such as power surges.

5) DIP SWITCHES

The device includes a 2-way Dip Switch that can be used to 

set some operating modes.

DIP 

SWITCH

SETTINGS

DIP1-DIP2

DESCRIPTION

DIP 1

OFF

Normal mode

ON

Master code programming 

mode, within 30s of switching

DIP 2

OFF

Turns off lights (OUT2) when 

key E is held down for 2 seconds.

ON

Turns on lights (OUT2) when 

key E is held down for 2 seconds.

6) DIAGNOSTICS FIG.C 

The reader includes 6 signal leds (L1-L2, on the internal circuit 

and RDY, FBk, ERR and Ok, on the front of the reader) for 

complete user diagnostics. 

When the reader turns on, blue RDY, yellow FBk and red ERR 

leds repeatedly blink.

The reader has a buzzer that signals the results of each user 

action for immediate feedback.

LED

COLOUR

MEANING

L1

green

It turns on to indicate relay output 

OUT 1 was activated and remains on 

for the entire activation time

L2

green

It turns on to indicate relay output 

OUT 2 was activated and remains on 

for the entire activation time

RDY

Blue

The led is normally on if the reader 

is powered. It turns off during the 

programming procedure. It turns 

off for 1 second if relay outputs are 

activated.

ERR

Red

It blinks once to signal incorrect code 

reading or entry. 

It blinks twice to indicate the cancel-

lation of code entry operations from 

the keyboard or programming pro-

cedures. When programming user 

codes: it blinks 4 times to indicate 

a code already in the memory was 

read or entered; it blinks 3 times to 

indicate insufficient code memory 

Summary of Contents for AXXEDO Q.BO SA

Page 1: ...attentivement les Avertissements qui se trouvent l int rieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atenci n Leer atentamente las Advertencias en el interior Let op Lees de Waarsc...

Page 2: ...D812093 00100_01 2 AXXEDO Q BO SA V2 6 OR 67x2 V1 V1 4 8 32 V2 3 5 13 40 80 87 3 A B 1 2 3 4 5 6...

Page 3: ...A 4B 3 beep Timeout 30 2 Timeout 30 Timeout 30 NEW MASTER NEW MASTER CODE OK ON 1 2 ON 1 2 ON 1 2 beep beep MASTER MASTER CODE OK ON 1 2 Sensore di luce Light sensor Capteur de lumi re Lichtsensor Sen...

Page 4: ...TZER BORRADO C DIGOS DE USUARIO WISSEN GEBRUIKERSCODE x 2 1 MASTER MASTER 3 2 OK x 1 KO x 4 BADGE 1 CODE 1 OK Timeout 30 Timeout 30 Blu Bleu Bleu Blau Azul Blauw Verde Green Vert Gr n Verde Groen Ross...

Page 5: ...NE SENSORE LUCE AMBIENTALE ROOM LIGHT SENSOR PROGRAMMING PROGRAMMATION CAPTEUR LUMI RE AMBIANTE PROGRAMMIERUNG UMGEBUNGSLICHTSENSOR PROGRAMACI N SENSOR DE LUZ AMBIENTAL PROGRAMMERING OMGEVINGSLICHTSEN...

Page 6: ...ERTISSEUR SONORE AKTIVIERUNG DEAKTIVIERUNG BUZZER ACTIVACI N DESACTIVACI N ZUMBADOR ACTIVERING DEACTIVERING ZOEMER beep BUZZER OFF BUZZER ON Timeout 30 MASTER MASTER CODE OK 0 OK 1 OK L 1 2 3A beep be...

Page 7: ...30 Timeout 30 RESETMEMORIA solocodiciutenti MEMORYRESET onlyusercodes REMISE Z ROM MOIRE uniquementcodesutilisateurs RESETSPEICHER nurBenutzercodes RESETMEMORIA soloc digosdeusuarios RESETGEHEUGEN ui...

Page 8: ...2usciterel 2A30Vdc concontatto normalmenteaperto NA etemporizzazioneprogrammabile identificate con OUT1 comando apertura varco di ingresso OUT2 comando accensione luci scale La durata di attivazione t...

Page 9: ...zzazione delle uscite rel ecc in casodiinterruzionedellaproceduraper30secondi digitazione del tasto E oppure digitazione di un tasto o di un valore non ammessi il lettore segnaler un errore 1 Beep del...

Page 10: ...ostata l uscita rel OUT 2 non si attiver per verificare il livello di luminosit ambientale possibile digitare senza uscire dalla programmazione un nuovo valore seguito dal tasto 0 verificando l eventu...

Page 11: ...pounaprecedenteprogrammazione mantenerepremutoiltasto 9 finoaquandovieneemesso un secondo beep e si vede lampeggiare il led giallo 2 secondi Digitare 00 seguito dal tasto OK Il buzzer emette un Beep i...

Page 12: ...normallyopen contact NA and programmable timer identified with OUT1 entrance opening control OUT2 stairwell lights on control Each relay output timer can be set using the reader program ming function...

Page 13: ...new Master badge or enter a new Master Code on the keyboard and press OK The buzzer beeps followed by a high tone the yellow FBK led turns on The reader Is awaiting other programming commands The read...

Page 14: ...reading the Master badge or within 30 seconds of the previous programming Hold down the 4 key until a second beep sounds and the yellow led blinks 2 seconds Enter 0 OK to turn off the buzzer 1 OK to t...

Page 15: ...aliment avecunetension comprise entre 12 et 24 V cc 15 travers les bornes PWR 4 2 SORTIES Le lecteur dispose de 2 sorties relais 2A 30V cc avec contact normalement ouvert NO et minuterie programmable...

Page 16: ...indiquelapr sence d unelumi resuffisanteelless clairentquandm mependant 30secondesapr schaquesaisie silecapteurestd sactiv par la programmation elles sont clair es en suivant le capteur configur sur l...

Page 17: ...ur 1 la sortie relais OUT2 clairage lumi res escaliers estactiv esilalumi reambianteestinsuffisante nulle p nombre aveclavaleur 9 clairagedeslumi res escaliers n est activ e que si la lumi re ambiante...

Page 18: ...sonore met un bip la Led jaune FBK s claire fixement le lecteur attend d autres commandes de programmation Lelecteurretourneaufonctionnementnormalen clairant laLedPDYeten teignantlaLedjaune siaucuneop...

Page 19: ...Relaisausgang f r Befehl Einfahrt Klemme Beschreibung OUT2 Relaisausgang f r Befehl Treppenbe leuchtung 4 1 STROMVERSORGUNG Der Leser AXXEDO Q BO SA kann mit einer Spannung von 12 bis24Vac Vdc 15 ber...

Page 20: ...esg ltigenBenutzer Codes mitdarauffolgender ffnung der T r OUT 1 automatisch auch den Relaisausgang OUT 2 f r die Einschaltung der Beleuchtung zu aktivieren falls der Wert der Beleuchtung unter der ei...

Page 21: ...n soll von 00 bis 99 gefolgt von der Taste OK 00 bistabile Modalit t 05 0 5 Sekunden 10 1 Sekunde Default 99 9 9 Sekunden Der Buzzer erzeugt einen Beep Ton und die gelbe LED FBK leuchtet auf der Leser...

Page 22: ...ungsbefehle Der LeserkehrtzurnormalenBetriebsweisezur ck dieLEDRDY gehtanunddiegelbeLEDgehtan fallsnichtinnerhalbvon 30SekundenandereOperationenausgef hrtoderdieTaste E gedr ckt werden Reset Speicher...

Page 23: ...EllectorAXXEDOQ BOSAsepuedealimentarconunatensi n de 12 a 24Vac Vdc 15 mediante los bornes PWR 4 2 Salidas El lector cuenta con 2 salidas rel 2A 30Vdc con contacto normalmente abierto NA y temporizaci...

Page 24: ...diente ajuste puede ser realizado mediante el procedimiento de programaci n del lector Adem s los LEDS de retroiluminaci n del teclado se encien den con luz fija siguiendo el sensor de luz si el senso...

Page 25: ...adear 2segundos Introducir el valor del nivel de umbral de intervenci n del sensor de luz ambiental de 0 a 9 luego pulsar la tecla OK 0 Sensor y salida OUT2 deshabilitada 1 9 sensor activo predetermin...

Page 26: ...yelLEDamarillocomienceaparpadear 2segundos Introducir 00 y luego pulsar la tecla OK ElzumbadoremiteunPitido elLEDamarilloFBKseenciende con luz fija el lector est a la espera de otros mandos de program...

Page 27: ...de aanslu itklemmen PWR door een spanning van 12 tot 24Vac Vdc 15 worden gevoed 4 2 Uitgangen Delezerisvoorzienvan2relaisuitgangen 2A30Vdc meteen normaal geopend contact NO en een programmeerbare timi...

Page 28: ...ure van de lezer mogelijk De leds van de achtergrondverlichting van het paneel gaan branden en volgen de lichtsensor Na een druk op een toets gaan de leds 30 seconden lang branden ook al geeft sensor...

Page 29: ...geactiveerd standaardwaarde 5 Waarde 1 de relaisuitgang OUT 2 inschakeling traphui sverlichting wordt geactiveerd bij zwak geen omgevin gslicht halfdonker waarde 9 de relaisuitgang OUT 2 inschakeling...

Page 30: ...de lezer wacht op andere commando s voor de programmering De lezer hervat de normale functionering door de led RDY in te schakelen en de gele led uit te schakelen als binnen 30secondengeenanderehandel...

Page 31: ...lasciare radiocomandi o altri dispositivi di comando alla portata dei bambini onde evitare azionamenti invo lontari dell automazione L utilizzatoredeveevitarequalsiasitentativodiintervento oriparazio...

Page 32: ...void unintentional automation activa tion The user must avoid any attempt to carry out work or repair ontheautomationsystem andalwaysrequesttheassistance of qualified personnel Anythingwhichisnotexpre...

Page 33: ...tifs de commande la port e des enfants afin d viter des actionnements involontaires de l automation L utilisateur doit viter toute tentative d intervention ou r parationdel automatisationets adresseex...

Page 34: ...und gefertigt In dieser Dokumentation nicht angegebene Verwendungsweisen k nnten zu Sch den und Gefahren f hren Die Firma haftet nicht f r Sch den die auf die unsa chgem e Verwendung oder die Nichtbea...

Page 35: ...asidodise adoyfabricadoexclusivamente para el uso indicado en la presente documentaci n Usos noindicadosenlapresentedocumentaci npodr anda ar el producto y fuentes de peligro La Empresa no se responsa...

Page 36: ...het in deze documentatie aangegeven gebruik ontworpen en vervaardigd Niet in dezedocumentatieaangegevengebruikenzoudenschade aan het product en gevaar kunnen opleveren Het bedrijf ziet van elke veran...

Page 37: ...D812093 00100_01 AXXEDO Q BO SA 37...

Page 38: ...D812093 00100_01 38 AXXEDO Q BO SA...

Page 39: ...D812093 00100_01 AXXEDO Q BO SA 39...

Page 40: ...benelux be POLAND BFT POLSKA SP Z O O 05 091 Z BKI www bft pl CROATIA BFT ADRIA D O O 51218 Drazice Rijeka www bft hr PORTUGAL BFT SA COMERCIO DE AUTOMATISMOS E MATERIAL DE SEGURANCIA 3020 305 Coimbra...

Reviews: