Technical data
3-2
3.2
Electrical system, Optical and Mechanical
Data
Spectral sensitivity
UV
UV1
IR
IR2
IR3
280 to 420 nm
190 to 550 nm
300 to 1050 nm
300 to 2700 nm
1050 to 2700 nm
Angle of view
3 ° with SKL
Self-monitoring
Fully electronic, 1 x
per 800 ms
Operating voltage
24 V DC
Current consumption
approx. 200 mA per unit
Pre fuse
max. 1 A, slow
Design
In accordance with protection class III
SELV
Operating temperature
-20 °C to +70 °C (-4 °F to +158 °F)
Current output
0(4) to 20 mA (Ra<250 Ohm)
Current window variable by software
Fault output
24 V DC, short circuit-proof
Range changeover
External selection via 24 V DC signal
Flame relay
1 changeover contact, floating
wire break detection optional
max. 48 V switching voltage
max. 1 A switching current (fused
with 0.5 A)
max. 30 W switching power
Switching thresholds
programmable by software
Safety switch-off time
0.4 to 5 s, set to 1 s by factory
Fibre optic connection
M30 outer thread, metric