Technical data
3-1
3
Technical data
3.1
General characteristic features
Flame scanner with integrated amplifier and flame re-
lay
Tested by the German Technical Inspection Associa-
tion TÜV, approved by IECEx
For continuous, intermittent and 72-hours operation
Type UV, UV1: For monitoring gas and oil-fired burn-
ers in the UV range
Type IR (VIS-IR): For monitoring oil, coal and mixed-
fuel burners
Type IR2 (IR): For monitoring gas and oil-fired burn-
ers in the IR range
Type IR3 (IR):
For flames of all kinds (including resi-
dues, H
2
S and special gases)
Two-channel flame monitoring system
Sensitivity adjustable separately for both channels by
software
Analog output flame intensity 0(4) to 20 mA
Flame analysis possibility by software
LED status display for flame relay and flame intensity
No additional wiring to external flame amplifiers
Type of protection IP66
Suitable for safety related applocations up to SIL 3 (ac-
cording to IEC 61508)