Failures
8-1
8
Failures
Problem:
Display:
Cause:
Remedy:
No flame -
ON signal
after the
burner has
been
started
No analogue
signal
LED “Flame”
OFF
LED sensi-
tiveity I/II
OFF
Flame ampli-
fier is not op-
erational
Check power supply
Check fuse F1 (T 0.5
amps)
Replace flame ampli-
fier
Check electrical con-
nection
1.bar is on
(FF)
LED “Flame”
OFF
Flame signal
too low
Check flame scanner
Check / set sensitivity
2.bar is on
(FD)
Flame scan-
ner or cable
defect
Check flame scanner
Check cable
3.bar is on
Clock cycle is
too long
Send unit to the repair
center
4.bar is on
Clock cycle is
too short
Send unit to the repair
center
5.bar is on
(MP)
Monitor chan-
nel and proc-
ess channel
are unequal
Send unit to the repair
center
Analogue
signal 25 -
100 %
LED “Flame”
ON
Relay contact
or wiring prob-
lem
Check fuse F102 (T 1
amp)
Check electrical con-
nection
Burner trips
Analogue
signal falling.
Below 25 %,
switch off RF
+ RM.
No flame,
weak flame
signal
Check flame
Check flame scanner
Check flame scanner
alignment, sight tube
and lens
Increase sensitivity
setting
Replace flame scan-
ner
Replace flame ampli-
fier
Check electrical con-
nection
Table 8
Summary of Contents for 3016
Page 2: ...ii ...
Page 20: ...Safety 2 8 ...
Page 26: ...Technical data 3 6 ...
Page 34: ...Transport installation and connection 4 8 ...
Page 46: ...Maintenance and servicing 7 2 ...
Page 48: ...Failures 8 2 ...
Page 50: ...Order data 9 2 ...
Page 54: ...Accessories 10 4 ...
Page 55: ...Accessories 10 5 ...