Fault finding
19-15
•
RXD/ RXD on CONN4 of the Comms module should be
connected to TX/ TX on CONN2 of all the motherboards.
TXD/ TXD on the Comms module should be connected to
RX/ RX of all the motherboards.
•
Check that each Controller motherboard in the branch has a
unique address on SW1/SW2.
•
If you can’t get one or more Controllers to communicate after
checking all the above, remove the RS485 connectors from all
the motherboards except one, power up the Controller with the
Comms module in it and check that it can communicate with
just the one Controller. Reconnect the controllers one at a time
until you find the Controller which is not working. You will
probably find that the connections are reversed on a part of
the branch, or, it is possible that a single Controller is faulty.
Summary of Contents for 4101-2
Page 2: ......
Page 12: ...4101 2 Controller Installation Handbook viii...
Page 14: ...4101 2 Controller Installation Handbook 1 2...
Page 24: ...4101 2 Controller Installation Handbook 2 10...
Page 46: ...4101 2 Controller Installation Handbook 4 8...
Page 68: ...4101 2 Controller Installation Handbook 7 8...
Page 88: ...4101 2 Controller Installation Handbook 8 20...
Page 110: ...4101 2 Controller Installation Handbook 14 6...
Page 122: ...4101 2 Controller Installation Handbook 16 4...
Page 123: ...Binding posts Earth pin of CONN4 Binding posts...
Page 124: ...0 Connect screen to nearest binding post 1 2 3 04 5 6 7 87 9 3 7 1...
Page 126: ......
Page 127: ...9 9 2 5 6 0 6 7 2 3 5 8 1 7 2 8 1 5...
Page 128: ...3 3 9 3 8 9 3 6 9 6 8 6 9 9 9 4 3 6 9 9 2 5 1 3 6 9 2 5 2 5 8 1 8...
Page 129: ...8 1 8 1 7 2 8 1 5 9 3 3 3 8 1 9 2 3 5 8 1 8 2 9 3 5 3 8 1 9 A 9 3 2 5 2 5 A 8 1 9 9...
Page 131: ...9 6 8 3 6 8 9 A 3 3 9 8 8 3 9 8 9 8 9 6 9 9 9 8 8 6 9...
Page 132: ...8 6 9 4 9 4 0 4 1 8 4 9 9 8 8 9 3 D 3 E 8 8 7 9 9 9...
Page 148: ...4101 2 Controller Installation Handbook 19 16...
Page 154: ...4101 2 Controller Installation Handbook A 1 6...
Page 156: ...4101 2 Controller Installation Handbook A 2 2...