FENIX2 Monitoring system – Commissioning instruction
Products
System structure
FENIX2
FENIX2 is a control unit with connections for 1-2 fire dampers and smoke
detector circuits that are automatically detected during commissioning.
FENIX 0-10 V module
When using regulating fire dampers, regulation can be performed in two
different ways, either via a local 0-10 V signal out at the damper or via master
communication (Modbus TCP or BACnet IP). If local control is desired with
0-10 V, the FENIX 0-10 V module is used to separate the local control signal,
from, e.g. a room sensor, and the 10 V signal from FENIX2 that takes over
during a functional test to check that the dampers can open.
1. Installation
Install FENIX2 with the requisite fasteners. A wall mount frame is fitted on the
units at the factory and should be used to maintain the IP65 enclosure class.
The FENIX 0-10 V module is mounted on a wall or cable ladder. Power sup-
ply cables and end position indication from the damper motor are connected
directly to the damper module. The FENIX 0-10 module in turn is connected
directly to FENIX2.