FENIX2 Monitoring system – Commissioning instruction

Products 

System structure 

FENIX2

FENIX2 is a control unit with connections for 1-2 fire dampers and smoke 
detector circuits that are automatically detected during commissioning. 

FENIX 0-10 V module

When using regulating fire dampers, regulation can be performed in two 
different ways, either via a local 0-10 V signal out at the damper or via master 
communication (Modbus TCP or BACnet IP). If local control is desired with 
0-10 V, the FENIX 0-10 V module is used to separate the local control signal, 
from, e.g. a room sensor, and the 10 V signal from FENIX2 that takes over 
during a functional test to check that the dampers can open. 

1. Installation

Install FENIX2 with the requisite fasteners. A wall mount frame is fitted on the 
units at the factory and should be used to maintain the IP65 enclosure class.

The FENIX 0-10 V module is mounted on a wall or cable ladder. Power sup-
ply cables and end position indication from the damper motor are connected 
directly to the damper module. The FENIX 0-10 module in turn is connected 
directly to FENIX2.

Summary of Contents for Fenix 2

Page 1: ...21 01 2021 FENIX2 Monitoring system Commissioning instruction FIRE SAFETY www bevent rasch com...

Page 2: ...contains electronic components that can be damaged if used incorrectly When connecting dampers smoke detectors and other con nections the unit must be powered down The cover to access the terminal bl...

Page 3: ...Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX2 that takes o...

Page 4: ...ector RCRD DAMPER DAMPER 3 DAMPER DAMPER 4 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V Connections in RCHD Connections in RCHD Connecti...

Page 5: ...ting of the terminals the panel enters Night mode whereby all dampers close without the controller generating alarms Used for example during intermittent operation Night mode can also be a good safety...

Page 6: ...arted Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the trou...

Page 7: ...box On Off Damper in middle position Open damper DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLA...

Page 8: ...r a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be a...

Page 9: ...to be replaced This can also be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected whe...

Page 10: ...10 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Page 11: ...11 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Page 12: ...191203 0001_ENG January 2021 teamfront se www bevent rasch com...

Reviews: