INTEGRATED ELECTRICAL CABINET
Installation, Operation, and Service Manual
Copyright
2016:
Bevco Engineering Company, Inc.,
W222N5739 Miller Way, Sussex, WI 53089 USA
IECAX480V125A OM1_R51 Siemens IEC Manual for AX Systems
Page 5 of 14
3.0 SPECIFICATIONS
•
ELECTRICAL SPECIFICATIONS:
UL design and ratings of this panel require the application of wire at the 75°C ampacity ratings
of NEC table 310.16. Wire rated at higher temperature ratings, such as 90°C, may be used
but ONLY applied at the 75°C ampacity ratings of NEC Table 310.16.
Catalog Number
Incoming Voltage &
Frequency
Incoming Power
Configuration
Main Circuit
Breaker Rating
Regulatory
Markings
IECAX480V125A
480VAC, 50/60Hz
3Ø + N
125 Amps
cULus
Short Circuit Current Rating is 35,000 Amperes RMS Symmetrical @ 480V
•
SEISMIC SPECIFICATIONS:
This Integrated Electrical Cabinet has been certified by
an independent California structural engineer
in
conformance with the shake testing requirements of
ICC-AC 156. The California OSHPD number is OSP-
0457-10.
The seismic performance characteristics are as follows:
S
DS
(g)
≤ 2.56; z/h ≤ 1.0 ; I
p
≤ 1.5
•
ENVIORNMENTAL SPECIFICATIONS:
FOR INDOOR USE ONLY
Temperature 59-90
°
F (15-32
°
C)
Humidity 30-75%, NON-CONDENSING
•
ELECTRICAL WIRING DIAGRAM:
The Electrical Wiring Diagram is shipped along with the disconnect panel inside the enclosure
door for convenient reference to the circuitry.
PARTS, TECHNICAL SUPPORT AND SERVICE
FOR INQUIRIES DURING INSTALLATION
CONTACT BEVCO ENGINEERING,
SUSSEX WI (262) 820-2400
FOR ISSUES FOLLOWING INSTALLATION,
CONTACT SIEMENS UPTIME CENTER,
(800) 888-7436