UT340, UT360, UT380, and UT3100
Planning and Installation Manual
5
103 Specifications for the UT380 and UT3100
Tables 5 - 8 contain specifications for UPS models UT380 and UT3100.
Table 5: AC Input Specifications, UT380 and UT3100
UT380 UT3100
Voltage 3 x 480Y/277 3 x 480Y/277
Rated input current - Amps 127 159
Mains tolerance % (programmable) +10, -15
+10, -15
Bypass tolerance % (programmable) ±10 ±10
Frequency - Hz 60 ±6% 60 ±6%
Current distortion % - THD 0 - 5 0 - 5
Acceptable cable size range - AWG
1, 2, 3, 4, 5
2/0 - 4/0 3/0 - 250 kcmil
Recommended overcurrent protection - Amps
4, 5
175 200
Table 6: AC Output Specifications, UT380 and UT3100
UT380 UT3100
Voltage 480Y/277 480Y/277
Rated output current - Amps 96 120
Tolerance % - symmetrical load
- asymmetrical load
6
- load step 0-100%
±1
±3
±5
±1
±3
±5
Distortion %, linear load 0 - 3 0 - 3
Frequency - Hz - mains synchronized
- free running %
60 ±6%
±0.1
60 ±6%
±0.1
Overload capacity % mains operation - 1 minute
- 10 minutes
250
150
250
150
Overload capacity % battery operation - 1 minute
- 10 minutes
150
125
150
125
Acceptable cable size range - AWG
1, 2, 3, 4, 5
1 - 2/0 1/0 - 3/0
Recommended overcurrent protection - Amps
4, 5
125 150
Notes for Tables 5 and 6:
1 Bus bar can accept up to 2 cables per terminal.
2 Based upon UL rating of termination connector and upon 75
o
C copper conductors at 30
o
C ambient from NEC Table 310-16.
Conductor size may vary based on installation requirements.
3 For a 100% switch mode load, it is recommended that you size the neutral cable for 1.732 times the phase current.
4 For units with external bypass, see Figures
5 For UPS module only (UPS input breaker).
6 100% imbalance, provided output current rating is not exceeded.