UT340, UT360, UT380, and UT3100
Planning and Installation Manual
3
102 Specifications for the UT340 and UT360
Tables 1 - 4 contain specifications for UPS models UT340 and UT360.
Table 1: AC Input Specifications, UT340 and UT360
UT340 UT360
Voltage 3 x 208Y/120 3 x 480Y/277 3 x 208Y/120 3 x 480Y/277
Rated input current - Amps 146 63 219 95
Mains tolerance % (programmable) +10, -15 +10, -15
+10, -15
+10, -15
Bypass tolerance % (programmable) ±10 ±10 ±10 ±10
Frequency - Hz 60 ±6% 60 ±6% 60 ±6% 60 ±6%
Current distortion % - THD 0 - 5
0 - 5 0 - 5
0 - 5
Acceptable cable size range - AWG
1, 2, 3
3/0 - 250 kcmil 4 - 2 300 - 500 kcmil 1 - 2/0
Recommended overcurrent protection -
Amps
3, 4
200 80 300 125
Table 2: AC Output Specifications, UT340 and UT360
UT340 UT360
Voltage 208Y/120 480Y/277 208Y/120 480Y/277
Rated output current - Amps 111 48 167 72
Tolerance % - symmetrical load
- asymmetrical load
5
- load step 0-100%
±1
±3
±5
±1
±3
±5
±1
±3
±5
±1
±3
±5
Distortion % - linear load 0 - 3 0 - 3 0 - 3 0 - 3
Frequency - Hz
- mains synchronized
- free running %
60 ±6%
±0.1
60 ±6%
±0.1
60 ±6%
±0.1
60 ±6%
±0.1
Overload capacity %, mains operation
- 1 minute
- 10 minutes
250
150
250
150
250
150
250
150
Overload capacity %, battery operation
- 1 minute
- 10 minutes
150
125
150
125
150
125
150
125
Acceptable cable size range - AWG
1, 2, 3
1/0 - 3/0 6 - 3 4/0 - 300 kcmil 3 - 1
Recommended overcurrent protection -
Amps
3, 4
150 60 225 90
Notes for Tables 1 and 2:
1 Based upon UL rating of termination connector and upon 75
o
C copper conductors at 30
o
C ambient from NEC Table 310-16.
Conductor size may vary based on installation requirements.
2 For a 100% switch mode load, it is recommended that you size the neutral conductor for 1.732 times the phase current.
3 For units with external bypass, see Figures
and
4 For UPS module only (UPS input breaker).
5 100% imbalance, provided output current rating is not exceeded.