Wiring diagram
The diagram below shows how to wire 8KW and 9KW electrified locks.
Figure
1—Wiring diagram for 8KW and 9KW electrified locks (9KW with RQE shown)
Run wires through the door or
mount wires to the door sur-
face with wire molding.
To find the correct wire gauge
for wire runs, see Figure
2 on
the reverse side.
RQE
(Request-to-exit) wires
are normally used with
access control systems.
8WDTL
Door transfer loop
Electrified cylindrical
chassis — 9KW shown
with RQE
RQE
(Request-to-exit) wires
Brown
(common)
Orange
(NO)
Green
(NC)
Power Supply
24 Volts AC or DC
*Note
: In some door applications (for
example fire doors), it may not be
possible to make extra holes into the
door. In such scenarios, the TCM may
be installed in a secure location at no
more than 20 feet from the door.
Ceiling
Electrical requirements
The following table describes the voltage and current specifications
for the 8KW and 9KW locks, with RQE (REX) switch, and
door monitoring switch.
Unit
Voltage
Current
8KW (RQE not avail-
able)
24 volts AC or DC 0.18 amp continu-
ous duty
9KW with and with-
out RQE
24 volts AC or DC 0.18 amp continu-
ous duty
RQE switch
30 volts AC or DC
maximum
0.7 amp inductive
0.7 amp resistive
T56090/Rev D 1800760 ER-7991-19 Jan 2015
Wiring Instructions for 8KW and 9KW Series
Electrified Cylindrical Locks with Request-to-exit
— Over
TCM
(Temperature
Control Module)
Insert TCM into the
1“ dia extension.*
(1” dia x 3” deep hole)