3.4
Parameters
3.4.1
General parameters
General parameters allow to set the detection characteristics of the sensor and are described as follows:
Name
BUSing Address
Values
From 0 to 255
Description Not used
Name
Advanced: smoothing
Values
From 0 to 10
Description
It is the value that represents the persistence of the detected movement. This value can range between 0
and 10. The greater value, the more continuous the movement must be for activation to occur. This value
must be lesser than or equal to half the Control Cycles parameter.
Recommended values depending on usage:
Movement detection (example: activate lighting): 2.
Intrusion detection: 8.
Name
Brightness threshold.
Values
From 0 to 100
Description
Initial brightness threshold factor for brightness dependent switching of channel 2 (value x 10 = lux).
For example: 100 = 1000 lux