5
Wiring diagram:
see Fig. 10
Wiring diagram description
1. Cable terminal
2. Spark generator
3. Ignition spark
L. Black
N. White
T. Green (earth)
Room ventilation – Location and venting.
ATTENTION:
An exhaust fan may be used with the appliance; in each case it shall be installed in
conformity with the national standards in force.
ATTENTION: Exhaust hood operation may affect other vented appliances; in each case it shall be
installed in conformity with the national standards in force.
Conversion to different types of gas
Before carrying out any maintenance work, disconnect the appliance from the gas and electric
supply. For Natural Gas fit regulator assembly described in Fig. 5. For LP Gas fit assembly described
in fig. 5.
- CHANGING THE NOZZLES FOR USE WITH OTHER TYPES OF GAS:
To change the nozzles of the burners use the following procedure:
Lift up the burners and unscrew the nozzles ( Fig. 7) using an adjustable spanner of 7 mm and change the
nozzles with those designed for the new gas supply according to the information given in TABLE A shown
below.
TABLE A: Adapting to different types of gas
Burner
Position
Injector
Gas
Pressure
Max Rate
Min Rate
By-pass
diam. [mm.]
Type
[i.w.c.]
[BTU/h]
[W]
[BTU/h]
[W]
diam. [mm]
0,90 Natural 4" 3400 996 900 264
Regulated
Auxiliary
Front R
0,54 LP
(Propane)
11"
3400
996
900
264 0,29
Semi-
Rear L and
1,18 Natural 4" 6100 1787 1500 439
Regulated
Rapid
R
0,70 LP
(Propane)
11"
6100 1787 1500
439 0,37
1,55 Natural 4" 10400
3047 3700 1084
Regulated
Rapid
Front L
0,92 LP
(Propane)
11"
10400 3047 3700 1084 0,58
1,65 Natural 4" 11900
3487 5300 1553
Regulated
Triple Ring
Central
1,02 LP
(Propane)
11"
12300 3604 5300 1553 0,73
CAUTION: save the orifices removed from the appliance for future use
Regulation of burners
Regulation of the "MINIMUM" on the burners
To regulate the minimum on the burners carry out the following procedure indicated below:
1) Turn on the burner and put the knob onto position MINIMUM ( small flame ).
2) Remove the knob ( Fig. 8) of the tap which is set for standard pressure. The knob is found on the bar of
the tap itself.
3) Beside the tap bar on the work top, insert a small slotted screwdriver into the hole on the vale rod (Fig. 8)
and turn the choke screw to the right or left until the flame of the burner is regulated in the most suitable way
to MINIMUM.
4) Make sure that that the flame does not go out when changing the position quickly from MAXIMUM to the
MINIMUM position.
ATTENTION: The regulation described above can be carried out only with burners using natural gas,
while with burners using propane gas the screw must be fully screwed in, in a clockwise direction.
Adaptation of the pressure regulator for use with different type of gas
The pressure regulator supplied with the appliance is a convertible type pressure regulator for use with
Natural Gas at a nominal outlet pressure of 4” w.c. or LP gas at a nominal outlet pressure of 11” w.c. and it is
pre-arranged from the factory to operate with one of these gas/pressure as indicated in the pre-arranging
labels affixed on the appliance, package and Instruction booklet.