Specifications
Important
Installation or repair should only be done by a qualified service person. The heater should be
inspected before use and at least annually by a qualified service person.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of ½ psig (3.5
kPa)
The appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.5 kPa)
-
Power & Gas Specifications
Gas Supply (Natural Gas ONLY)
HAB-M20
HAB-M40
HAB-M50
Rated Input
High Fire Rate 20,000
40,000
50,000
Low Fire Rate 15,000
32,000
42,000
Inlet Pressure
Maximum
14.0” W.C.
14.0” W.C.
14.0” W.C.
Minimum
7.0” W.C
7.0” W.C
7.0” W.C
Manifold Pressure
Maximum
6.2” W.C.
6.3” W.C.
6.3” W.C.
Minimum
3.0” W.C.
4.5” W.C.
4.5” W.C.
Inlet Connection
½” Male NPT
Electrical Supply
Alternating current AC, voltage; 24 V, 60 Hz with L, N and Ground (GND).
Note:
24V transformer not supplied.