Lighting & Shutdown Instructions
-
Lighting
1. Open manual gas supply valve (ensure gas supply lines have been purged).
2. Turn on switch to energize electric supply.
3. The electronic control module will time begin the ignition period in 3 seconds.
4. The gas valve will open and ignition spark will commence and continue for 20 sec.
5. If flame starts and “is detected”, flame will continue until turned off.
6. If no flame is detected, the gas valve will close after 20 sec. A “wait’ period commences and
lasts approximately 5 sec. and a second trial for combustion commences. The electronic
control will attempt three trials for ignition before locking out for approximately 1 hour at which
time it will automatically try again.
Electronic control of heater can be re-set by de-energizing and re-energizing electric power.
-
Shut Down
1. Turn off power to electronic control.
2. For longer periods of shut down, also close manual gas supply valve.
Note:
It is recommended to use a factory recommended “Hi-Lo switch” with this heater.
March, 2013
BERNER PATIO+ Luminous