Bernard Integral+ Commissioning Instructions Download Page 17

15

Case N°2:actuator starts closing, stops on the close limit switch, and the LED

indicating closing is still on.
Turn actuator potentiometer progressively to off the LED.

9.7 Adjustment of 100%
The local/off/remote selector must be on remote position. Move local control switch to
position 100% for the actuator to receive an opening command (20mA).

Case N°1:actuator starts opening and stops before the open limit switch.

Turn potentiometer "ADJ 100%" (adjustment of 100%) progressively clockwise
to bring the actuator on the open limit switch. Turn slowly this potentiometer in
opposite direction until the green LED goes off.

Case N°2:actuator starts opening, stops on the open limit switch, and the green LED

is still on.
Turn potentiometer "ADJ 100%" (adjustment of 100%) progressively counter-
clockwise to off the green LED.

9.8 Split Range

The positioner card can be configured for split range.

Split range means input signals 4-12mA and 12-20mA. The end user signal is normal :4-
20mA. A first actuator is set to receive a signal from 4 to 12mA and a second actuator is
set to receive a signal from 12 to 20mA. Each actuator receives the signal 4-20mA. The
first one opens completely from 0 to 50% of the signal and the second from 50 to 100%
of the signal.

Switch 1

Switch 2

Move switch 1 to position B for the actuator to receive an input signal 12-20mA.
Move switch 2 to position B for the actuator to receive an input signal 4-12mA.

9.9 Operation with a transmitter 4-20mA
In standard the actuator potentiometer is used to know the valve position.

Switch 7

Move switch 7 to position B for operation with a transmitter 4-20mA instead of the actuator
potentiometer. The CI2701 board can provide the power supply to the transmitter TAM or
FSG.

Summary of Contents for Integral+

Page 1: ...NESSE CEDEX FRANCE T l 33 01 34 07 71 00 Fax 33 01 34 07 71 01 E mail mail bernard actuators com Commissioning instructions f Commissioning instructions for or INTEGRAL INTEGRAL contr control and ol a...

Page 2: ...OTE SELECTOR PADLOCK 8 7 INDICATIONS 8 7 1 BLINKING INDICATIONS 9 7 2 INDICATION RELAY N 1 9 7 3 INDICATION RELAY N 2 9 7 4 INDICATION RELAY N 3 10 7 5 INDICATION RELAY N 4 10 7 6 FAULT MONITORING REL...

Page 3: ...otentiometer for setting of dead band Potentiometer for setting of 100 Potentiometer for local control Local control switch Lamp indicates thermal sensor tripped Lamp indicates torque switch tripped S...

Page 4: ...s and jumpers are in position A 3 POWER SUPPLY 3 1 Actuator power supply Actuator power supply can be 3 phase single phase or DC F Jumper 100 support located on lower board The electronic board includ...

Page 5: ...ing on torque switch The limit switch is used for valve closed indication and also allows to detect stopping on torque switch at mid stroke as a fault and stopping on torque switch in closed position...

Page 6: ...th the electronic board CI2701 can be done from an external voltage supply or an internal voltage supply Inputs on the board are completely isolated by opto isolators Pulse commands with self holding...

Page 7: ...sing of the valve Contact open opening of the valve One must configure the actuator for priority to close see 5 4 5 4 Priority to Open or to Close In standard there is no priority to open or to close...

Page 8: ...a contact Jumper on support 27 position Jumper support 27 Move jumper on support 27 position to have ESD by opening a contact Caution In this configuration if ESD input is not connected the actuator r...

Page 9: ...choose between remote and local control The button for local control open close allows to operate the actuator in the appropriate direction Local stop is done by a momentary rotation of the local rem...

Page 10: ...ly closed Note Voltage free relays are always with normally open contact One reversing relay for fault monitoring Note The monitoring relay is normally energised and drops in case of fault Relays info...

Page 11: ...lay N 1 to indicate torque switch open In standard relay N 1 is with contact normally open Jumper on support 22 in position Jumper support 22 Move jumper on support 22 position for relay N 1 to be wit...

Page 12: ...upport 18 to position OPENING for relay N 3 to indicate that actuator is running in opening direction Move jumper on support 18 to position RUNNING for relay N 3 to indicate that actuator is running I...

Page 13: ...n abnormal operation The fault monitoring relay is normally energised and is disenergised in case of fault The relay is disenergised upon the following events Loss of main power supply control voltage...

Page 14: ...s case there is no fault indication 8 FUSES PROTECTION Accessibility Switch off power supply on actuator Remove cover on terminal box Unfasten the 4 screws located near the covers screws Move a few ce...

Page 15: ...2 Operation with signal 0 10 V Switch 4 Switch 8 Switch 9 Switch 10 Move switches 4 8 9 and 10 to position B for operation with signal 0 10 V The output signal is 0 20 mA 9 2 Operation direction confi...

Page 16: ...the dead band turn it counter clockwise Caution Reducing the dead band too much will provoke hunting on the actuator 9 5 Local operation One can simulate an input signal 4 20 mA locally to check the...

Page 17: ...essively counter clockwise to off the green LED 9 8 Split Range The positioner card can be configured for split range Split range means input signals 4 12mA and 12 20mA The end user signal is normal 4...

Page 18: ...TO ON OFF CONTROL The function LOCAL CONTROL INHIBITION cannot be used with a positioner 10 OPTION TIMING CONTROL BOARD The timing control board allows to reduce the operating speed of the actuator to...

Page 19: ...T Single phase or DC position M The TH light on the Integral board configuration panel indicates thermal tripping of thermal protective device The Actuator will again be available after the motor has...

Page 20: ...doubt check rotational direction To reverse the motor rotational direction change over wires 2 and 3 of the motor terminal strip Adjust the opening limit switch The opening limit switch must be actua...

Page 21: ...The electronics further only stores the data for the torque limiter corresponding to the rotational direction The torque limiter data are stored electronically To clear a torque limiter memory a reve...

Page 22: ...ck fuses of Integral board and replace as required Check position of jumper 100 on the Integral board Three phase position T Single phase or DC position M The TH light on the Integral board configurat...

Page 23: ...to A Switch 10 set to A 0 10 V signal Switch 4 set to B Switch 8 set to B Switch 9 set to B Switch 10 set to B Check setting of Auto 0 100 switch on the positioner board Check the reference signal usi...

Page 24: ...must be observed In case of doubt check rotational direction To reverse the motor rotational direction change over wires 1 and 2 of the motor terminal strip Check closing configuration switch 1 of the...

Page 25: ...n The torque limiter data are stored electronically To clear a torque limiter memory a reverse order must be sent Send a control signal on the input Set the selector switch to remote PROBLEM The Actua...

Page 26: ...tc com 3 Fl SungWon Building www humanitc com 813 1 Bangbae Dong Seocho Gu SEOUL 137 832 Tel 82 2 532 2604 Fax 82 2 3478 7089 MALAYSIA ACTUATION CONTROLS ENGINEER tcmeng pc jaring my 7 Jalan Bayu 2 5...

Reviews: