Installation of Recessed Back Box

in New Construction

1. Mounting Back Box (See Figure 1).

a. Place the back box between two 16"  (406 mm)   center-to-

center wall studs at the desired mounting height but no closer 
than 8" (203 mm) to adjacent wall of floor.

b. Align back box such that the bottom and sides will be flush with 

finished wall surface (top flange of wall box should protrude 
approximately 1/2" (12.7 mm) from finished wall surface).

c. Secure the back box in position with wood screws or nails as 

shown in Figure 1.

2. Power Supply Wiring (See Figure 1)

NOTE: Wire compartment volume - 119in3 (1950cm3).
a. Run a power supply cable into the knockout area in the upper 

right hand corner of the back box.  All wiring must be in 
accordance with National and Local Electrical Codes. Refer to 
Table 1 for correct wire size.

b. Remove disconnect switch bracket by loosening two screws on 

the right side.

c. Install a cable clamp in the “knockout” in the top of the back box.
d. Insert power supply cable through cable clamp, allowing at least 

6" (152mm) of leads to extend inside the back box. Connect the 
blue lead wires of disconnect switch to the supply wire leads 
using wire connectors wiring diagram, pg. 3).

e. Ground the back box using the green screw located in the inside 

top of the housing.

f. Secure disconnect switch bracket in place by tightening screws.

Installation of Recessed Back Box 

in Existing Construction

1. Provide a wall opening 14-1/2"  (362mm) wide by 18-1/2" 

(470mm) high at the desired mounting height, but no closer than 
8" (203mm) from floor. (See Figure 2.) 

2. Power Supply Wiring

NOTE: Wiring Compartment Volume - 119in3 (1950cm3).
a. Run a power supply cable into the area above the top of the wall 

opening. All wiring must be in accordance with National and 
Local electrical codes. Refer to Table 1 for correct wire size.

b. Remove disconnect switch bracket by loosening the two screws 

on the right side.

c. Install a cable clamp in the “knockout” in the top of back box.
d. Insert power supply cable through cable clamp, allowing 

approximately 6"  (152mm) of cable length to remain inside the 
back box to facilitate connections.

3. Mounting Back Box

a. Place the back box into wall opening flush with finished wall 

surface on bottom and sides of box. (Top flange of back box 
should protrude approximately 1/2" or 12.7mm from finished 
wall surface).

b. Secure the back box in place with wood screws or nails.

4. Wiring Disconnect Switch

a. Connect the power supply wires to the blue wires of the 

disconnect switch using wire connectors (see wiring diagram, 
pg. 3.)

b. Ground the back box using the green ground screw located in 

the inside top of the box.

c. Secure disconnect switch bracket in place by tightening screws.

Installation of Back Box with 

Surface-Mounting Frame (See Figure 3)

1. Secure back box to wall with knockouts in upper right hand 

corner using screws and anchors.

2. Hang the surface-mounting frame on the back box. Ensure that 

the back edge of the surface-mounting frame is flush against the 
wall.

NOTE: If heater is located in a high traffic area, where it may be 
subjected to vandalism or abuse, take extreme care to see that the
box is firmly attached to the wall.

3. Power Supply Wiring

NOTE: Wiring Compartment Volume - 119in3 (1950cm3).
a.Run a power supply cable into the area to the upper  right 

corner of the mounting frame. Arrangement of wiring to this 
point must be in accordance with National and Local codes. 
Refer to specifications on page 2 for proper wire size.

NOTE: If the wiring is to run through the wall, cut a hole in the area 
of  the  top  of  the  back  box.  Run  the  supply  wire  through  this  hole.

Then remove the “knockout” from the 

top of the box and proceed

to step C.

IMPORTANT

CAUTION

WARNING

DO NOT INSTALL HEATER UPSIDE DOWN OR SIDEWAYS.
DO NOT USE HEATER WITHOUT GRILLE.

FOR WALL MOUNTING ONLY. DO NOT INSTALL HEATER CLOS-
ER  THAN  8"  (203  mm)  TO  THE  FLOOR  OR  ANY ADJACENT
WALL SURFACE.  DO NOT INSTALL CLOSER  THAN  36"  (915
mm) TO THE CEILING.

Fig. 1: Locating Recessed Back Box in New Construction

Back Box

Fig. 2: Locating Recessed Back Box in Existing Construction

VOLTS

277
208
208

240/208

240/208
277/240

208
208

240/208

240

277/240

WATTS

3000/1500
4000/2000

4000

4000/3000
2000/1500
4000/3000
4000/3000
2000/1500

4800
4800

4800/3600

4800

4800/3600

MODEL #

FRA3027B
FRA4020B

FRA40203B

FRA4024B

FRA40243B 

FRA4027B

FRA4820B

FRA48203B

FRA4824B

FRA48243B

FRA4827B

PH

1
1
3
1

3
1

1
3
1
3
1

WIRE SIZE

12 AWG
10 AWG
14 AWG
10 AWG
12 AWG
14 AWG
12 AWG

10 AWG
12 AWG
10 AWG
14 AWG
10 AWG

2

8” (203mm) MIN

!

BTU/HR

10,239/5120
13,652/6826

13,652

13,652/10,239

6826/5120

13,652/10,239
13,652/10,239

6826/5120

16,382
16,382

16,382/12,287

16,382

16,382/12,287

AMPS

10.8/5.4
19.2/9.6

11.1

16.7/14.45

8.3/7.2

9.7

14.4/12.5

7.2/6.3

23.1
13.4

20.0/17.3

11.6

17.3/15.0

TABLE 1

BACK

BOX

!

!

Fig. 3: Surface Mounting Installation

MOUNT BACK BOX

TO WALL USING

REAR MOUNTING

HOLES.

HANG FRAME

ON BACK BOX.

15-5/32 "
(385mm)

19" 

(482mm)

3-13/16"

(97mm)