Beretta Power Plus Box 150 Installation Manual Download Page 46

 

46

Nr.

No. on the PC

Cause

Troubleshooting

A10

10

Internal error

Replace the Slave card.

A11

11

Internal software error

Press the rest button.

A12

12

Internal error

Replace the Slave card.

A16

16

The limit thermostat contact is 

open with the burner off

Connector disconnected or defective.

Limit thermostat defective.

A17

17

Delivery sensor error due to 

exceeding the limit temp.

Check that the flow rate in each unit’s water circuit is 

sufficient.

A18

18

Return sensor error due to 

exceeding the limit temp.

Check that the flow rate in each unit’s water circuit is 

sufficient.

A19

19

Flue gas sensor tripped for 

overtemperature > 80°C (fan 

operates at maximum speed)

Heat exchange insufficient on the flue gas side inside 

the exchanger.

Clean the flue gas side exchanger.

A20

20

The flame goes out too late 

after the gas valve closes

Check the proper operation of the gas valve.

Replace the gas valve.

A21

21

Internal error

Replace the Slave card.

A22

22

The slave board has gener-

ated a type "E” error for more 

than 24 hours

Check the history of "E" type errors

A23

23

Internal clock error

It is an error inside the clock.

Can be caused by a transient power failure.

Perform a manual reset to restore functioning.

A24

24

Fan error

The measured fan speed varies too much with the 

read speed.

Check the fan.

Check the fan's electrical connection.

Replace the fan.

A25

21

Internal error

Replace the Slave card

Nr.

No. on the PC

Cause

Troubleshooting

E33

33

Line and neutral inverted

Restore the correct line-neutral electrical connection

E34

34

Reset button error.

It was pressed more than 7 

times in 30 min.

Wait for the error to disappear.

If the error did not disappear after max 40 min, replace 

the Slave card.

E35

35

Water differential pressure 

switch error

(contact open)

Check that the flow rate in each unit’s water circuit is 

sufficient.

Replace the water pressure switch (tar.500 lt/h).

E36

36

Internal error

Replace the Slave card.

E37

37

Flame detection error

Clean the electrodes.

Replace the electrode.

E38

38

Flue gas sensor short circu-

iting

Check the flue gas sensor connector.

Replace the flue gas sensor.

E39

39

Flue gas sensor with contact 

open

Check the flue gas sensor connector.

Replace the flue gas sensor.

E40

40

The frequency is not 50 Hz

Check the frequency of the electrical network

E41

41

Internal error

Replace the Slave card.

E42

42

Flow sensor in short circuit

Check the delivery sensor connector.

Replace the delivery sensor.

E43

43

Delivery sensor with contact 

open

Check the delivery sensor connector.

Replace the delivery sensor.

E44

44

Return sensor short circuiting Check the return sensor connector.

Replace the return sensor.

E45

45

Return sensor with contact 

open

Check the return sensor connector.

Replace the return sensor.

E46

46

Delivery sensor error due to 

exceeding the limit temp.

Check that the flow rate in each unit’s water circuit is 

sufficient.

E47

47

Return sensor error due to 

exceeding the limit temp.

Check that the flow rate in each unit’s water circuit is 

sufficient.

E48

48

Flue gas sensor error due to 

exceeding the limit temp. (fan 

turns at max with this error).

Check that the flow rate in each unit’s water circuit is 

sufficient.

Clean the water side and flue gas side exchanger.

E49

49

Insufficient or absent earth 

connection.

Check the earth connection.

Replace the Slave card.

Summary of Contents for Power Plus Box 150

Page 1: ...Installation Manual THERMAL MODULES CONDENSING Power Plus Box Installation Manual EN...

Page 2: ...r condensing systems comply with Directive 2009 142 EC Gas Appliances Directive 92 42 EEC on efficiency requirements and Annex E and Pres Republic Decree n 412 26 Au gust 1993 Electromagnetic Compatib...

Page 3: ...ensions and weights 23 2 4 Handling 24 2 5 Installation premises 24 2 6 Installation in older systems and systems requiring modernisation 24 2 7 Water connections 25 2 8 Flue gas evacuation for instal...

Page 4: ...Centre B 1 2 Precautions The operation of any appliance that uses fuel electrical power and water demands that a number of fundamental safety precautions be respected a Do not allow children or infirm...

Page 5: ...uation and condensate outlet mani folds can have an outlet to the left or to the right Power Plus Box 150 Base module consisting of 3 heat generators for heating and DHW production systems Heat input...

Page 6: ...ima di installare e mettere in servizio l apparecchio Laterale DX Temperatura ambiente min 10 C max 50 C Questo apparecchio pu essere installato e funzionare all aperto o solo in locali permanentement...

Page 7: ...ld 9 System return manifold 10 Single heating element flue gas analysis outlet 11 Fan 12 Single heating element flue gas exhaust union 13 Automatic bleed valve 14 Safety thermostat 15 Drain cock 16 Ma...

Page 8: ...R PLUS BOX 200 POWER PLUS BOX 200 POWER PLUS BOX 150 SZ1 Delivery manifold sensor SZ2 Low system temperature sensor SB Boiler sensor SE Outdoor sensor PZ1 Zone 1 circulator high temperature PZ2 Zone 2...

Page 9: ...Tm 50 C 60 C 40 C 106 6 Chimney loss with burner operating 1 3 Chimney loss with burner off 0 1 Casing loss Tm 70 C 0 5 Flue gas temperature Return temperature 5 C C CO2 at minimum 9 0 G20 10 4 G30 3...

Page 10: ...re rating P1 48 9 65 1 kW EFFICIENCY at rated thermal input and at high temperature rating 4 88 4 88 4 at 30 of rated thermal input and at low temperature rating 1 97 8 97 8 ADDITIONAL ENERGY CONSUMPT...

Page 11: ...ater and minimum pressure switch 7 Circulator or 2 way valve 8 Gas valve 9 Flue gas exhaust union with check valve and flue gas analysis outlet 10 Manual diverting valve 11 Return shut off valve 12 Ga...

Page 12: ...P available for system circulation 1 heating element Circulator characteristic curve Heating element pressure drop at 2000 l h 550 mbar Flow rate necessary for every heating element 2000 l h b At the...

Page 13: ...8 18 61568 1 26135 20 12090 39 6033 58 3216 77 1817 96 1079 17 58719 2 25044 21 11634 40 5828 59 3116 78 1766 97 1051 16 56016 3 24004 22 11199 41 5630 60 3021 79 1717 98 1024 15 53452 4 23014 23 1078...

Page 14: ...J2 J8 J10 R4 2 3 J3 J6 J5 J7 F1 Fuse 3 15 A 1 R6 R5 MC R3 R2 On Valv Mix Alarm Comune J12 2 BUS J14 1 R1 4 3 T1 Ebus contr remoto 24V contr remoto Comune Analogic Input Comune T A circ 1 Comune T A c...

Page 15: ...entaz Sens Hall Soffiante Input Sens Hall Soffiante Comune Sens Hall Termostato limite Valvola gas 2 1 3 a 9 m J16 NTC fumi J9 J4 a 10 WD J5 T3 PC Main SLAVE 3 IG3 C TS VG SM SR SF EA ER J10 J17 a m 1...

Page 16: ...that can be deactivated automatically ON in case of permanent errors 6 Single heating element slave reset button 7 Instrument panel 8 FOURTH heating element switch only for Power Plus Box 200 9 THIRD...

Page 17: ...er is shut off is 6 minutes When the last burner is turned off the circulator only stops when the room thermostat demand stops The ignition shut off control function in both cascad ing management mode...

Page 18: ...es and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by pressi...

Page 19: ...he desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc for 10 secs...

Page 20: ...and change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s the secon...

Page 21: ...identifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with the first...

Page 22: ...anty certificate Barcode labels 6 Accessory envelope containing Natural gas to LPG transformation kit valid for Eu rope Door key The following is also supplied positioned on the base inside the modula...

Page 23: ...5 RI 1530 MI GAS SC SF RI MI GAS DESCRIPTION Power Plus Box 150 200 MI System delivery manifold 5 DN 125 PN 6 DN RI System return manifold 5 DN 125 PN 6 DN GAS Gas manifold 3 DN 80 PN 6 DN SF Flue Man...

Page 24: ...collecting condensate and for flue gas exhaust see the specific chapter Flue gas evacuation for installations in central heating plants b Take into consideration the space that is required in order t...

Page 25: ...hydraulic separator near the system s delivery and return manifolds To make it easier to position the modular system in the area of installation refer to the Handling paragraph Adjust the feet of the...

Page 26: ...tinguishing polypropylene class B1 implemented with pipes with socketed connections or equivalent lines The maximum equivalent length of the flue gas evacuation lines is indicated in the table Each mo...

Page 27: ...1 1 b If installing in a central heating plant it is recommended to direct both the products deriving from the boiler con densate outlet as well as the condensate deriving from the flue gas manifold...

Page 28: ...t at least for one heating season in the case of maximum formulation of condensate The operation can be checked easily using the pH indica tor cards available commercially They can be purchased from a...

Page 29: ...diagram on the following page referring to the wiring diagrams Provide a three pole cable 8 to supply the 230V 50Hz line direct it through the hole made in the casing of the electric panel and connect...

Page 30: ...Respect the connection L line N neutral Keep the earth conductor 2 cm longer than the power supply conductors Use cables with a section greater than or equal to 1 5 mm2 complete with cable terminal ca...

Page 31: ...ement and adjust parameter 39 to make any necessary correction b The connection cable between the outdoor sen sor and the control panel must not have couplings If these are necessary they must be wate...

Page 32: ...o or three turns 3 Open the filling tap 4 provided on the system until the pressure indicated on the pressure gauge is 1 5 bar Close the filling tap 4 4 b Deareation of the Power Plus Box modular syst...

Page 33: ...rtant to first check that the heating system shut off and gas taps are open the type of gas and the supply pressure comply with the features of the modular system the hydraulic circuit pressure when c...

Page 34: ...rom the second modular system on wards To do so see the paragraph Setting addresses for cascade coupling If there is a low temperature system set parameter 34 1 4 8 7 2 6 3 1 5 Adjust the room thermos...

Page 35: ...ight will flash To change this value press or To confirm press OK The system will turn on in DHW mode until the demand is satisfied When the modular system is in stand by the Master unit display will...

Page 36: ...nerate a high temperature heating demand at maximum power Proceed as follows press the Set esc and buttons at the same time for 5 seconds generate the heat demand using the room thermo stat The system...

Page 37: ...ith G20 natural gas with a flue gas exhaust line with L 15m parameter 36 01 b All checks must be performed by Technical Assis tance Centre 3 3 Adjusting the functional parameters The heating functions...

Page 38: ...20 CLIMATIC CURVE HIGH TEMPERATURE circuit T_CH_High Max heat requirement T_CH_High_foot T_out_min 2 Setpoint_T_CH_Low Low temperature circuit setpoint parameter 3 If the fixed point operating mode is...

Page 39: ...There are 2 cases Fixed point operation Par 14 0 Operation with climatic control Par 14 1 FIXED POINT OPERATION PAR 14 0 With the high temperature circuit attenuation disabled Par21 0 when the high t...

Page 40: ...he setpoint is calculated based on the outdoor temperature If the outdoor temperature Tout_min Par 37 preset to 0 C then setpoint setpoint_T_Ch_low If the outdoor temperature Tout_max Par 38 preset to...

Page 41: ...prevents burner ignition and shut off in the case of a low heat demand The conditions for low load operation activation is controlled in every Slave card that sends the function activation request to...

Page 42: ...Voltage Volt 0 1 2 3 4 5 6 7 8 9 10 Fig 2 The burner ignited when Delivery temp Setpoint_ch_high Par 1 Ch_high_ hist_on Par 19 Delivery temp Setpoint_ch_low Par 3 Ch_low_ hist_on Par 26 The burner sh...

Page 43: ...nit goes below 0 5 bar 3 7 Setting addresses for cascade coupling If it is necessary to implement multiple modular systems with a cascading connection the second modular system on wards must be discon...

Page 44: ...must not be changed 1 2 3 4 OFF ON Master Slave Slave Slave Master Slave Slave Slave FIRST modular system SECOND modular system BLOCK 1 BLOCK 2 J14 Slave 1 2 3 4 OFF ON Address for BLOCK 1 Address for...

Page 45: ...laves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E34 42 I...

Page 46: ...as pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min replace the Slave card E35 35 Water differential pressure switch error contact op...

Page 47: ...tpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Priority 0 0 2 Hot water system priority 0 1 Hot water functioning with heating until reaching...

Page 48: ...Mixer valve stand by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 0 0 1 Third pump setpoint 0 Main pump of s...

Page 49: ...em and remove the one for G20 remove the gas label from the outside Gruppo termico regolato per G30 G31 28 30 37 mbar Paese di destinazione Paese di destinazione Tipo di apparecchio Caldaia categoria...

Page 50: ...refully retighten the cap 1 3 12 Temporary shutdown In the case of temporary absences weekends short trips etc proceed as follows set the room thermostats to approx 10 C set parameter 2 to 10 or adjus...

Page 51: ...Do not use fuels sponges impregnated with abrasive solutions or powder detergents INSIDE Before starting internal cleaning operations close the gas shut off valves close the system taps Access to the...

Page 52: ...10 11 12 13 Once the maintenance operations are complete refit the components working in the opposite direction of what was described Disassembling the circulator open the two front doors in the casi...

Page 53: ...on of the electrode and replace it if necessary 22 17 21 23 Once the maintenance operations are complete refit the components working in the opposite direction of what was described b Check that the g...

Page 54: ...t upon con sent of the modular system control Gas valve Check for the presence of 230Vac voltage on the gas valve terminals check wiring and connections The modular system does not start No electric p...

Page 55: ...circulator Check the electrical connection of the circulator Frequent tripping of the system safety valve System safety valve Check calibration or efficiency System circuit pressure Check the circuit...

Page 56: ...to add water to central heating systems Use a manual device in stead and record top ups in the system service book b If there are more than one boiler they must all be put into service either contemp...

Page 57: ...is therefore important to avoid two factors possibly leading to the above mentioned pro cesses i e contact between air and water in the installation and regular topping up with fresh water To elimina...

Page 58: ...transmitted by ISPESL memorandum no 102 99 dated 13 12 99 taking into account the positive results of the checks and tests carried out at the manufacturer s laboratory we believe that multiple elemen...

Page 59: ...59...

Page 60: ...oilers com Beretta reserves the right to modify the characteristics and specifications given in this publication at any time and without prior notice as part of its policy of continuous product improv...

Reviews: