7
EN
Boiler ignit. dynamic
20-500 K
100K
Modulation dynamics parameter; best to leave default value
Boiler switching off
dynamic
20-500 K
100K
20
Modulation dynamics parameter
T-reset
5-500
50
Modulation dynamics parameter; best to leave default value
On modulat. value
50%-100%
80%
Previous module value to connect next module
Min modulation value
10%-60%
30%
15
Minimum modulation value module disconnection; not
possible to set parameter <15%
Min modul value
00%-60%
30%
Modulation minimum value required to activate next module
AC modulation value
40%-100%
80%
Modulation rated value for modules (with AC values only –
not cascade – do not touch)
(GC) Sequence1
-
1 2 3 4 5 6 7 8
Cannot be changed
(GC) Sequence2
-
8 7 6 5 4 3 2 1
Cannot be changed
Next mode
Sequence1
Sequence2
Timed
1/2 switch
Rotating
Sorting
1
SELECT MODE
Switchover order in sequence 1
Switchover order in sequence 2
Switchover between sequence 1 and 2 according to number
hrs. in service (change time)
For 2 modules with different capacity: lowest number of
modules activated to satisfy request
Change time up, 1st boiler in the cascade active sequence
becomes the last
Change in succession of 1st generator based on n. working
hrs. after change time
Time sequen. change
0-800 hrs
0 hrs
SELECT Sequence change time
Idle time
00min-30 min
00min
Waiting time before connecting/disconnecting module
(00=10sec)
Leave value with F key [end]
fig. 4