EXCLUSIVE

FUNCTION NOT ACTIVE

DAILY FUNCTION

WEEKLY FUNCTION

ANTI-LEGIONELLA

INSTALLER

5.2.4  Time band schedule function (room thermostat)

It is possible to set a time schedule for heating function and for the 

storage 

tank filling (is installed) from the boiler.

Whenever  the  heating  system  is  managed  by  a  room  thermostat,  and 

therefore without any time schedule, it is possible to tie the heat requests 

coming  from  the  device  to  programmable  time  bands  by  setting  the 

parameter POR = 1 (see section 

“5.2.2 Configuration of the zone”), 

in other 

cases it is always enabled.

To access this function:

 -

select MENU on the main page of the REC10 and press 

“ok”

18/05/2013

12:17

30

°C
.3

1.3 bar

MENU

INFO

SET

FRI

HOT WATER TEMPERATURE

STATE

PLANT

MON

 - using the 

“up”

 and 

“down”

 keys select TIME SCHEDULE confirming 

the selection

SETTINGS

MENU

SELECT OPTION

TIME SCHEDULE

From this menu it is possible to access the display and adjustment of the 

time  schedule  for  the  heating  functions  of  the  zone  rather  than  for  the 

domestic 

storage tank. For each day of the week it is possible to set up to 

4 bands, characterised by a starting time and an end time. 

Note:

 for more details on the use of the programming timing see the USER 

MANUAL of the REC10.

MON

18/11/2013

12:17

MAIN

SELECT THE ZONE

SCHEDULE

07:30
11:30
18:00

08:30
13:30
22:30

SELECT

A DAY

START

MAIN 

THURSDAY

END

ZONE SCHEDULE

5.2.5  Setting the thermoregulation

Thermoregulation  only  works  with  the  outdoor  temperature  sensor 

connected  and  active  only  for  the  HEATING  function;  therefore,  once 

installed,  connect  the  outdoor  temperature  sensor  to  the  specific 

connections on the boiler terminal board.

This enables the THERMOREGULATION function.

The temperature measured by the outdoor temperature sensor is displayed 

on the initial page in the top right, alternating with the display of the time.

When thermoregulation is enabled (outdoor temperature sensor present), 

the algorithm for automatically calculating the outlet setpoint depends on 

the type of heat request.

In any case, the thermoregulation algorithm will not directly use the outdoor 

temperature,  but  rather  a  calculated  outdoor  temperature  that  takes  into 

account  the  building’s  insulation:  in  buildings  that  are  well  insulated,  the 

outdoor temperature variations will have less impact than those that are 

poorly insulated by comparison. Enabling THERMOREGULATION occurs 

in the following way

:

 -

access the technical parameters as explained in the section 

“4.1 Access 

to the technical parameters”

 -

select  THERMOREGULATION  with  the 

“up”

 and 

“down”

  keys, 

confirming the selection

.

PARAMETERS

THERMOREGULATION

RANGE RATED

TECHNICAL

INSTALLER

CALIBRATION

INSTALLATION

Using the REC10 it is possible to set the value of the following parameters:

BUILDING TYPE

It

 

is  indicative  of  the  frequency  with  which  the  value  of  the  calculated 

outdoor temperature for thermoregulation is updated, a low value for this 

value will be used for buildings that have little insulation.

Setting range:  

[5min - 20min]

Factory setting: 

[5min]

REACTIVITY EXT SENSOR

It

  is an indication of the speed with which variations of the measured 

outdoor temperature affect the calculated outdoor temperature value for 

thermoregulation, low values indicate high speeds.

Setting range:  

[0 - 255]

Factory setting: 

[20]

At this point, to change the value of the previous parameters, proceed as 

described below:

 -

access the technical parameters as explained in the section 

“4.1 Access 

to the technical parameters”

 -

in  sequence  select  THERMOREGULATION  and  TYPE  OF  BUILDING 

rather than REACTIVITY EXT SENSOR with the 

“up”

 and 

“down”

 keys, 

confirming the selection

 - set the desired value with the 

“up”

 and 

“down”

  keys,  confirming  the 

selection.

Note:

  The  value  of  the  calculated  outdoor  temperature  used  by  the 

thermoregulation  algorithm  is  displayed  in  the  INFO  menu  under T  EXT 

FOR THERMOREG.

HEAT REQUEST FROM THERMOSTAT or POR (Programmable Timer)

In  this  case  the  outlet  setpoint  depends  on  the  outdoor  temperature  for 

obtaining a reference ambient temperature of 20°C. There are 2 parameters 

that compete to calculate the output setpoint:

 -

slope of the compensation curve (KT)

 - offset on the reference ambient temperature

.

Summary of Contents for EXCLUSIVE R

Page 1: ...EXCLUSIVE R Installer and user manual RO MANUAL DE INSTALARE SI UTILIZARE EN ES INSTALLER AND USER MANUAL MANUAL DE INSTALACI N Y USO...

Page 2: ...o Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings and sa...

Page 3: ...qualified personnel a a Any technical or cleaning operation is forbidden before disconnecting the appliance from the main power supply by turning the system s main switch to OFF and the main switch o...

Page 4: ...ion of the instrument for the combustion analysis check In fig 6b is shown a sample drawing where the distances between boiler and cabinet niche were obtained using a 300mm length tool Longer lengths...

Page 5: ...60 100 mm vertical 11 m 9 m 1 3 m 1 6 m Concentric pipe 80 125 mm 25 m 20 m 1 m 1 5 m Twin pipe 80 mm 70 70 m 35 35 m 1 m 1 5 m b b Straight length means with terminals and joints but without bends b...

Page 6: ...ons open the caps of the lower A automatic air vent valve by two or three turns to allow a continuous venting of the air leave the plug of the valve A open make sure the cold water inlet tap is open o...

Page 7: ...g disabling the key lock function is achieved by pressing the button A for more than 10 seconds During this step all of the LEDs C will flash for 1 second 3 11 6 Changing the operating mode In normal...

Page 8: ...l as the outdoor temperature if available On the left and right sides are displayed the icons indicating the status of the system their meaning is as follows Pressing the keys up and down it is possib...

Page 9: ...T 80 5 C AT 45 C BT INSTALLER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE Only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE Only mixing zones with ACTUATION BE16 VALVE RUN 120...

Page 10: ...y if managed by the control board THERMOREGULATION INSTALLER CLIMATIC CURVES MAIN MAIN ZONE1 ZONE2 INSTALLER FIXED SET POINT 80 5 C AT 45 C BT MIN CH SET MAX CH SET INSTALLER If EXTERNAL PROBE NOT con...

Page 11: ...NT 50 C 37 5 C 60 C INSTALLER Only if HEAT PUMP enabled to DHW TANK FROST PROTECT 7 C 0 C 100 C SERVICE Only if HEAT PUMP enabled to DHW TANK FR PROT OFFSET 5 C 1 C 20 C SERVICE Only if HEAT PUMP enab...

Page 12: ...C INSTALLER MIN EMERG OUT T 10 C 20 C 10 C INSTALLER BOILER INTEGR DELAY 30min 1min 240min SERVICE HP INTEGR DELAY 30min 1min 240min SERVICE BOILER WAITING 2min 1min 60min SERVICE HEAT PUMP WAITING 2m...

Page 13: ...orrectly that conditions for regular maintenance are guaranteed if the boiler is placed inside or between items of furniture the seal of the fuel adduction system that the fuel flow rate corresponds t...

Page 14: ...ER OFF CH 3MIN RESET TIMERS CH This parameter allows you to reset the REDUCED HEATING MAXIMUM OUTPUT TIMING during which the speed of the fan is limited to 75 of the maximum heating output that has be...

Page 15: ...ING NAME This parameter allows you to attribute a specific name to the heating zone POR This parameter allows you to enable the central heating programming timing for the zone concerned if the heat re...

Page 16: ...depends on the type of heat request In any case the thermoregulation algorithm will not directly use the outdoor temperature but rather a calculated outdoor temperature that takes into account the bui...

Page 17: ...16 C that can vary within the range 5 5 5 3 First commissioning Position the system s master switch to the on position Open the gas tap to allow fuel to flow Adjust the room thermostat to the desired...

Page 18: ...ected When an outdoor temperature sensor is installed the outlet temperature is automatically selected by the system which quickly adjusts the ambient temperature according to the variations in the ou...

Page 19: ...he up and down keys and confirm the selection to deactivate the function INSTALLER SCREED HEATING FUNZIONE GIORNALIERA DEACTIVATE FUNCTION ACTIVATE FUNCTION The screed heating function when active is...

Page 20: ...from the cover of the instrument panel to access the electrical components AKM0x X17 X14 1 1 X12 X23 X16 X2 X21 X8 X13 X19 X9 X25 X11 X18 X22 1 1 1 1 1 1 1 1 6 1 5 12 10 4 3 5 4 6 5 6 X15 X1 X4 X6 1 3...

Page 21: ...pplied with the settings indicated in the multigas table It is nevertheless possible according to the system requirements or the regional regulations on the combustion gas emission limits to set that...

Page 22: ...k button it is possible to return to the main screen where a fault is signalled by this flashing icon 18 05 2013 12 17 MENU INFO SET 42 C 1 3 bar FRI PLANT HOT WATER TEMPERATURE STATE The user can ret...

Page 23: ...0 5 sec on 0 5 off definitive E030 fan fault ON definitive E040 water transducer load the system ON definitive E041 water transducer load the system flashing 0 5 sec on 0 5 off transitional E042 water...

Page 24: ...to OFF set the system s main switch to off close the fuel and water taps of the heating and domestic hot water system In this case the anti freeze and anti blocking systems are deactivated Drain the h...

Page 25: ...REC10 MASTER and finish the operatione NEW to set a new system configuration restoring the factory setting of the parameters NEW FROM AKM SELECT THE TYPE OF CONFIGURATION ON OFF Closing position 5 20...

Page 26: ...TI ZONE CONTROLLER REC10 V01 26 PRESS ANY KEY TO CONTINUE SELECT THE TYPE OF CONFIGURATION NEW FROM AKM 5 23 Replacing the AKM01 board The configuration operations should be carried out by professiona...

Page 27: ...umption at maximum and minimum output checking the position of the ignition flame detection glowplug checking the gas failure safety device b b After carrying out the maintenance operations the analys...

Page 28: ...ING function enabled If a heating request from the main zone is in progress the icon will be flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic...

Page 29: ...ing ok to confirm the selection Pressing back takes you back to the initial screen without making any selection BOILER STATE MAIN ZONE 9 1 Boiler This function can be selected in order to set the boil...

Page 30: ...n If the selection is cancelled or the back key is pressed you return to the previous SET screen SET THE PARAMETER WILL BE CHANGED CONFIRM CANCEL CONFIRM OR DELETE SELECTION 10 2 Domestic hot water on...

Page 31: ...st the current time is replaced with the boiler flow temperature and turns on the icon concerning the type of request in progress A message for the system efficiency level can be displayed in the top...

Page 32: ...D THURSDAY MODIFY DELETE COPY 07 30 11 30 18 00 END 08 30 13 30 22 30 SELECT OPTION Press the up and down keys to select the desired time band and press ok to confirm the selection START MAIN THURSDAY...

Page 33: ...O MODIFY In order to confirm that the operation has been completed successfully the display will show the list of days to which the scheduled programme has been copied MAIN SCHEDULE OF THURSDAY WILL B...

Page 34: ...h check the system flashing 0 5 sec on 0 5 off transitional boiler board communication lost ON transitional BUS 485 communication lost ON transitional List of combustion faults ERROR CODE ERROR MESSAG...

Page 35: ...REC10 after which the machine must be disconnected from the power supply to reset the number of attempts available b b Request the intervention of the Technical Assistance Centre E020 LIMIT THERMOSTAT...

Page 36: ...6 5 107 8 103 9 105 8 105 9 107 4 103 2 101 0 Useful efficiency Pn max 30 30 return 109 8 105 8 109 3 106 6 Efficiency at average P Range Rated 80 60 98 0 97 8 Efficiency at average P Range Rated 30 3...

Page 37: ...20 G31 G20 G31 Maximum CO s a less than p p m 140 150 220 220 CO2 9 2 10 2 9 0 10 0 NOx s a lower than p p m 40 60 40 30 T flue gases C 63 64 65 70 Minimum CO s a less than p p m 10 15 20 40 CO2 9 1 1...

Page 38: ...fan rotations rpm 1 500 1 900 Minimum number of DHW fan rotations rpm 1 500 1 900 b b DHW functions refer only if a storage tank is connected accessory available on request Parameter Symbol EXCLUSIVE...

Page 39: ...ner 9 Conveyor 10 Fan 11 Mixer 12 Ignition transformer 13 Flue gas exhaust 14 Degassing unit pipe 15 Flue gas probe 16 Upper air vent valve 17 Limit thermostat 18 NTC delivery probe 19 Flame ignition...

Page 40: ...bianco TBT OT SE TBT TA A B REC X11 X14 X25 M20 grigio grigio 1 10 viola viola rosso rosso nero alim blu sign marrone MOD 1 3 X19 T P 4 3 TBOL 1112 SBOL 6 1 X1 marrone blu 2 1 3 5 4 rosa blu P N L F 3...

Page 41: ...at exchanger 13 NTC delivery probe 14 Limit thermostat 15 Upper air vent valve 16 Air water separator 17 Water tank available by request 3 16 15 A B 1 C D 11 12 13 10 7 6 5 3 2 4 14 8 9 E F TA Room th...

Page 42: ...W pump modulation area graphic 1 setted to 7 metre circulator graphic 2 setted to 5 metre circulator graphic 3 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 0 100 200 300 400 500 600 700 80...

Page 43: ...43 EXCLUSIVE 5 A condensate drain B water gas 25R 35R C 275 350 A B C 6a 6b distances in mm measured in mm 6 Indoor installation Outdoor installation in a partially protected place...

Page 44: ...sensor 13 14 OT Open therm 15 16 SBOL Water tank probe 17 18 X1 Not used 19 20 X2 Not used 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1718 19 20 A B TA TBOL TBT SE OT SBOL X1 X2 M20 D Voltage free contac...

Page 45: ...IN PIPE 80mm 15 90 bend flange installed as standard A A C B COAXIAL PIPE 80 125mm flange installed as standard A A C B 90 bend flange installed as standard C B 90 bend A A adaptor flange installed as...

Page 46: ...50 60 70 80 90 20 15 10 5 0 5 10 15 20 25 30 D A E CURVE DI TERMOREGOLAZIONE Temperatura esterna C Temperatura di mandata C 20 30 40 50 60 70 80 90 100 20 0 2 0 4 0 6 0 8 1 0 1 5 2 0 2 5 3 0 T80 T45 1...

Page 47: ...25 130 135 140 145 150 155 160 165 170 175 Lunghezza tubo scarico fumi m Lunghezza tubo aspirazione aria m CaldaiaExclusive 25C n lunghezza massimatubi 80 mm EXCLUSIVE 25R flue gas pipe length m air s...

Page 48: ...information contained in this manual at any time and without prior notice Consumers statutory rights are not affected Cod 20097753 04 15 Ed 0 Cod 20127998 07 17 Ed 2 RANGE RATED EN 483 The max CH inp...

Reviews: