If the battery is damaged or is leaking, follow your site’s hazardous materials handling
procedures.
Replace the battery
We recommend that you replace Ranger Pro Gateway batteries in an indoor equipment room or
a similar environment. Do not replace batteries in a hazardous area. Use only approved battery
types described in the relevant Ranger Pro Gateway datasheet.
To dispose of used or partially expended batteries, follow your on-site or locally accepted
hazardous materials handling procedures.
Close the Device
To close the device:
1. Ensure that the Ranger Pro Gateway lid seal is clean before closing it.
2. Align and fasten the captive screws into the hinges using a cross-tightening technique
(do not tighten both screws on one side while leaving both screws on the other side loose).
DO NOT over-tighten the captive screws as this may compromise the lid seal. Fasten
captive screws to a torque of 6 Nm.
6.3 Update Gateway Software
You may on rare occasions need to update the Ranger Pro Gateway software. Request or
download software updates from Bently Nevada technical support. You can update Ranger Pro
Gateway software using the web-interface.
To update gateway firmware:
1. Use your browser to navigate to the IP address of your Ranger Pro Gateway and login.
2. Select
Maintenance
>
Software Upgrading
tab.
3. Click on the
Upload
file area to browse to and select the relevant gateway software file.
4. Wait for the upload to complete.
5. Click
Upgrade!
The upgrade is completed.
Click on
Remove Files
to remove all uploaded software files before uploading new files.
6.4 Reset Gateway
The Ranger Pro Gateway can be reset using the web-interface or using the power connector if in
a non-hazardous environment.
43/46
Ranger Pro ISA100 Wireless Gateway
User Guide
158M1430 Rev. -