600V/1000V DC Combiner Installation and Operating Instructions – 36-String Disconnect Models
950-002305-000 Rev A
31
Chapter 3: Installation Procedure
Figure 16
Area for cutouts when connecting wires through the sides of a combiner
in a fiberglass enclosure
provides the measurements for cutouts for the fiberglass enclosures.
Table 10
Measurements (in inches) for cutouts for fiberglass enclosures
Measurement
30x24-inch
Enclosure
A
Height of cutout on left side
26 1/2
B
Depth of cutout
4
D
Length of cutout on bottom
20 1/4
E
Depth of cutout on bottom
5
Cutouts should not be within 2-1/4 inches of the edges
of the enclosure.
Cutout area