BENNING IT 130
short instructions
- 10 -
1.6 Switch position „AUTO“
Turn the rotary selector switch to the "AUTO" position in order to select the measuring function by
means of the "Commander" probe tip (044155) or by means of the optional "Commander" test plug
(044149).
The following functions can be selected by means of the "Commander":
selection of the measuring function (only in the "AUTO" switch position)
start of measurement
storage of measuring results
LC display illumination ON/OFF
measuring point illumination ON/OFF
1.7 Settings
Turn the rotary selector switch to the "SETTINGS" position in order to make the following settings at
the tester:
MEMORY (request data, delete data, delete entire memory)
SELECT LANGUAGE (GB, D, E, F, NL)
SET DATE/TIME
EARTHING SYSTEM (TN/TT or IT network)
RCD TESTING (according to EN 61008/EN 61009, IEC 60364-4-41, BS 7671, AS/NZS 3017)
SET ISC FACTOR setting (0.20 - 3.00)
SELECT COMMANDER (ON/OFF)
INITIAL SETTINGS
CLAMP SETTINGS (BENNING CC 1 (044037) , BENNING CC 3 (044038))
1.8 Measured value memory
The internal memory of the tester allows to store up to 1800 measuring results including parameters,
limiting values and sate/time of the measurement.
The measuring results can be stored in a memory structure comprising 4 levels:
Memory structure:
Example of installation structure:
[OBJ] OBJECT 001
customer Meyer
[BLO] BLOCK 001
distributor of ground floor
[FUS] FUSE 001
F1 kitchen
[CON] MEASURING POINT 001
socket 1
Measurement: no.: 1/3 RCD I: 22.5 mA
no.: 2/3 R ISO: >999 M
Ω
no.: 3/3 R LOW: 0.17
Ω
The PC software BENNING PC-Win IT 130 (included in the delivery) serves to read the memory of
measured values of the tester (download) and to transmit installation structures that have already
been created on the PC to the tester (upload).