Switching thresholds of the input voltage monitoring:
1
Rated input voltage 48 V DC
Lower switch-off threshold U1
40.8 V
Switch-on threshold U2
49.0 V
Switch-on threshold U3
57.6 V
Upper switch-off threshold U4
60.0 V
The Inverter can be switched on only when the input voltage is UDC
≥U2.
7. Assembly and Commissioning
Attention!
The safety notes (See section 1) must be observed at all
times during assembly, installation and commissioning!
After installation, connecting and commissioning the inverter is ready for
operation without restriction. No additional settings and readjustments are
necessary during operation under all operating conditions.
The inverter is designed for operation in closed and dry environment. The
maximum permissible ambient temperature is +40°C (without de-rating). The
inverter is designed to operate in a controlled environment. Attention must be
paid that the inverter is not exposed to aggressive airborne substances and that
the passage of cooling air is not hampered.