Bennett Site Master Instruction Manual
Installation
11
ELECTRICAL RATINGS
Electrical Power
……240 WATTS, 115/120V 50/60hz
P4229
Sheet 1
Rev B
AC POWER CONNECTIONS FOR SITE MASTER SP
Read all safety instructions and notes shown in
Figure 1.5
and on wiring diagram 126000-P4229
before applying power to the Site
Master.
NOTES FOR POWER WIRING DIAGRAM
1.
All wiring must be installed and used in accordance with the national electrical code
(NFPA #70), Automotive and Marine Service Code NFPA #30), state, and local
electrical codes.
2.
All wiring gauge is minimum required, stranded wire with THHN insulation must be
used. Do not reuse old wire from an existing installation.
3.
Pull a Green 12 ga. stranded THHN ground wire through the junction box and wiring
through and secure at grounding post near the terminal strip in the Site Master’s
electrical enclosure. Terminate the other end at the main electrical service panel
ground bar. Do not terminate at the neutral bar of a sub-panel or rely on metal
conduit for this ground connection. Each Site Master’s grounding post must be
within 1-ohm resistance to earth ground potential. Do not use wire nuts on ground
circuits, use only compression type connectors. This is required to initiate Bennett’s
Limited Warranty.
4.
Use 15 Amp neutral breaking circuit breakers, which are supplied by the customer.
BREAKER IDENTIFICATION:
CB #1 Electronic Power – Hot for electronic power is 115 VAC 50/60 Hz
Note
: No more than 2 Site Master’s per breaker.
Figure 0.5 –AC Power Connection