MRCDB300 series

 MRCDB300-series_D00343_05_Q_XXEN/01.2022 

 5

LED flashing modes

  

slowly

 

error

 

 

  

medium

 

mode change

 

  

quickly

 

ready for address modification

 

  

slow flashing

 

address setting mode

 

  

once

 

confirmation

System state LED and output relays

The LED indicates the system state by means of colours and lighting/flashing. The changeover 

contacts of the relay outputs K1 and K2 have defined switching positions for each system state. 

System state

GREEN

 

LED 

ON

RED

 

LED

Alarm

Notes

Relay K1

Relay K2

Device switched off 

off 

off

Device is de-energised, no monitoring, no moni-
toring function.

de-energised de-energised

Normal operating state 

lights 

off 

The device is supplied with the specified voltage 
and monitors the primary circuit. No residual 
current flows which would lead to tripping.

energised

energised

Prewarning 

lights

flashes 

briefly 

The device is supplied with the specified 
voltage and monitors the primary circuit. A fault 
current flows which exceeds the set limit of the 
prewarning.

de-energised energised

Alarm state 

off 

lights 

The device is supplied with the specified voltage 
and monitors the primary circuit. A fault current 
flows which exceeds the set limit of the alarm.

de-energised de-energised

Device error 

off 

flashes  

slowly 

The device is supplied with the specified voltage 
and monitors the primary circuit. An error is 
detected by the periodic self tests. 

de-energised de-energised

Device in calibration mode

see manual for DC calibration procedure

de-energised de-energised

Device in address mode

see manual for procedure

Device signalling

flash quickly in 

alternation

Modbus register 20006 = 2  
Use to detect the device in its environment faster.
Is automatically deactivated after one minute. 

Reset

off

flashes  

slowly

State is reached by pressing and holding the "T" 
button during alarm state. To perform the reset, 
release the "T" button when the red LED flashes 
slowly (1,5…5 s).

Test

flashes  
quickly

off

State is reached by pressing and holding the "T" 
button in normal operating state. To perform the 
test, release the "T" button when the green LED 
flashes quickly (5…10 s).

switches

switches

A

B

C

D

E

Summary of Contents for MRCDB300 Series

Page 1: ...Quickstart guide EN MRCDB300 series_D00343_05_Q_XXEN 01 2022 MRCDB300 series AC DC sensitive residual current monitoring module for MRCD applications...

Page 2: ...e in earthed power supplies TN and TT systems up to 800 V is possible These devices are suitable for monitoring AC and DC fault currents type B Any other use than that described in this document is re...

Page 3: ...ts must be plugged together and calibrated during commissioning Device view 21 22 24 11 12 14 K1 K2 3 4 7 8 9 1 2 5 6 10 11 12 11 12 13 14 No Terminal Meaning 1 24V Supply voltage US 2 GND 3 D1 Contac...

Page 4: ...ce i The use of a type 2 surge protection de vice SPD is mandatory due to possible impulse voltages and in order to comply with normative requirements The surge protection device must be con nected up...

Page 5: ...s the set limit of the prewarning de energised energised Alarm state off lights The device is supplied with the specified voltage and monitors the primary circuit A fault current flows which exceeds t...

Page 6: ...ys switch to safe state during offset calibration system is switched off Procedure of the first offset calibration Action LED 1 Install the measuring current transformer in the system off 2 Plug the e...

Page 7: ...ls by an electrically skilled person to ensure that they are functioning properly This requirement is deemed to be satisfied for normal and environmental conditions if the test intervals mentioned in...

Page 8: ...CTBC120 when I n 100 mA 330 A CTBC120P when I n 100 mA 630 A CTBC210 when I n 300 mA 630 A CTBC210P when I n 100 mA 630 A CTBC210P when I n 300 mA 1000 A Measurement accuracy 1 of full scale value Te...

Reviews: