background image

4 MRCDB300-series_D00343_05_Q_XXEN/01.2022 

MRCDB300 series

Connection - N/C principle with contact feedback

Refer to the manual for further connection options.

Commissioning - Modbus RTU

Address setting

 

i

Every MRCDB3… has a factory-set Modbus address. The address is 1XX, where XX = the last 

two digits of the serial number. Example: Serial number = 123456

78 

 -> Modbus address = 178

The preset address can be changed via a COMTRAXX gateway, via Modbus or directly on the de-

vice. 
The address can be changed on the device before installation and offset calibration. The electron-

ic module must not be connected to the measuring current transformer during address setting. 

Each address in the bus system may only be assigned once.

 

i

The use of a type 2 surge protection de-
vice (SPD) is mandatory due to possible 
impulse voltages and in order to comply 
with normative requirements.  
The surge protection device must be con-
nected upstream of the power supply 
unit on the supply side.  
Features of the surge protection device:

 

– Nominal discharge current In (8/20 μs): 20 kA

 

– Response time: 25 ns

 

– Two-stage: 1 va 1 spark gab

 

– Alternatively, the power supply unit must be 

connected to a CAT II supply without a surge 
protection device.

U<

F 6 A

L1
L2
L3

N

DC 24 V

AC

DC

21

GND

T/R

GND

24 V

22 24

21

22 24

11

12 14

3

MRCDB30...-CTBC...

DG

D1

 

i

Within an interconnection of devices via 

the RS-485 interface, the first and the 

last device must each be provided with a 

terminating resistor.  

This device-internal resistor can be con-

nected by means of a wire jumper or a 

DIP switch.

X1 X2

120 Ω

120 Ω

DIP switch

COM465IP 

last device

MRCDB30... 

first device

Wire jumper

Summary of Contents for MRCDB300 Series

Page 1: ...Quickstart guide EN MRCDB300 series_D00343_05_Q_XXEN 01 2022 MRCDB300 series AC DC sensitive residual current monitoring module for MRCD applications...

Page 2: ...e in earthed power supplies TN and TT systems up to 800 V is possible These devices are suitable for monitoring AC and DC fault currents type B Any other use than that described in this document is re...

Page 3: ...ts must be plugged together and calibrated during commissioning Device view 21 22 24 11 12 14 K1 K2 3 4 7 8 9 1 2 5 6 10 11 12 11 12 13 14 No Terminal Meaning 1 24V Supply voltage US 2 GND 3 D1 Contac...

Page 4: ...ce i The use of a type 2 surge protection de vice SPD is mandatory due to possible impulse voltages and in order to comply with normative requirements The surge protection device must be con nected up...

Page 5: ...s the set limit of the prewarning de energised energised Alarm state off lights The device is supplied with the specified voltage and monitors the primary circuit A fault current flows which exceeds t...

Page 6: ...ys switch to safe state during offset calibration system is switched off Procedure of the first offset calibration Action LED 1 Install the measuring current transformer in the system off 2 Plug the e...

Page 7: ...ls by an electrically skilled person to ensure that they are functioning properly This requirement is deemed to be satisfied for normal and environmental conditions if the test intervals mentioned in...

Page 8: ...CTBC120 when I n 100 mA 330 A CTBC120P when I n 100 mA 630 A CTBC210 when I n 300 mA 630 A CTBC210P when I n 100 mA 630 A CTBC210P when I n 300 mA 1000 A Measurement accuracy 1 of full scale value Te...

Reviews: