Settings
40
isoPV1685-1685PFR_D00007_02_M_XXEN/10.2016
7.3 Factory settings
Parameters
Parameter
Condition
can be set via
Insulation response value
R
an1
10kΩ
BMS, CAN
Insulation response value
R
an2
1 kΩ
BMS, CAN
isoPV1685PFR only:
Residual current response value
I
Δ
n1
1 A
BMS, CAN
isoPV1685PFR only:
Residual current response value
I
Δ
n2
5 A
BMS, CAN
Fault memory insulation measurement
off
BMS
isoPV1685PFR only:
Fault memory residual current measure-
ment
off
BMS
isoPV1685PFR only:
Transformer monitoring
on
BMS
Relay K1 (11/12/14)
N/C operation
BMS
Relay K2 (21/22/24)
N/C operation
BMS
Relay K3 (31/32/34)
N/C operation
–
isoPV1685P(FR) only:
EDS mode
auto
BMS
isoPV1685P(FR) only:
PGH current
30 mA
BMS
isoPV1685PFR only:
Standby mode (disconnection from the
mains)
off
BMS
Reset to factory setting
---
BMS
BMS address
2
SS8103
BMS termination
ON
SS8100
CAN termination
ON
SS8102
Permissible system leakage capacitance
≤ 500 μF
SS8103
Measurement speed
Fast
SS8103