Operation and setting
32
isoPV_D00024_02_M_XXEN/07.2018
Pressing the "INFO" button provides the following information wit-
hout opening the menu:
•
Device name, firmware version
•
Response values Alarm1 and Alarm2
•
Leakage capacitance
C
e
(indication in case of insulation
values > 20 kΩ), measurement not possible when using
AMP3 and AMP4
•
Setup status (for details about the setup status refer to the
status table on Page 66
•
COM-Setup (isoPV's own bus address)
Please have the details above on hand if you have a problem and if you contact Bender
for technical questions.
Press the "TEST" button to start the self test of the
ISOMETER
®
.
Press the "RESET" button to reset insulation fault alarms
stored in the ISOMETER
®
. The memory function is only
available after activating the fault memory in the ISO SETUP menu or after bridging the
terminals R1/R2. Furthermore, the fault memory of the ISOMETER
®
can only be reset
when the measured insulation value is at least 25 % and when the
value is 1 kΩ higher than the set response value.
Press the "MENU" button to call up the menu system.
INFO
ESC
TEST
RESET
MENU