5. isoHV525-S4-4 parameter overview
5.1 Setting the response value
"R1" and "R2" are the two parameters that monitor the insulation resistance
R
F
.The va-
lue R1 can only be set higher than the value R2. If the insulation resistance
R
F
reaches or
falls below the activated values R1 or R2, this leads to an alarm message. If
R
F
exceeds
the values R1 or R2 plus the hysteresis value (see table below), the alarm will be cleared.
The parameters "U <" and "U >" can be activated or deactivated to monitor the nominal
system voltage
U
n
. The maximum undervoltage value is limited by the overvoltage val-
ue.
FAC
= Factory setting;
Cs
= Customer setting
5.2 Configuration of the relay operating mode
FAC
= Factory setting;
Cs
= Customer setting
Para-
meter
Activation
Setting
Description
Available via
FAC
Range
FAC
Cs
BMS Modbus
R1
on
R2 … 500
50
kΩ
Pre-alarm
R
an1
Hys. = 25 %/min. 1kΩ
X
X
R2
on
10… R1
25
kΩ
Alarm value
R
an2
Hys. = 25 %/min. 1kΩ
X
X
U<
off
30 … “U>"
30
V
Alarm value
Undervoltage RMS
Hys . = 5 %/min. 5 V
X
X
U>
off
"U<"… 1,10k
1100
V
Alarm value
Overvoltage RMS
Hys. = 5 %/min. 5 V
X
X
Relay K1
Relay K2
Description
Available via
FAC
Cs
FAC
Cs
BMS
Modbus
n.c.
n.c.
Relay operating mode (n.c./n.o.).
X
X