Settings
Settings
iso685-D-P_D00170_00_M_XXDE/06.2016
49
10.1
1.10.3.1
TEST
The functional test of the digital output can be activated or deactivated. This only applies
to the manual test and not to the cyclic device self test:
10.1
1.10.3.2
Mode
The following settings can be used to set the operating mode for the digital output:
10.1
1.10.3.3
Function 1
Refer to
.
10.1
1.10.3.4
Function 2
Refer to
.
10.1
1.10.3.5
Function 3
Refer to
.
•on
The manual test changes the status of the dig-
ital output.
•off
The manual test does not change the status of
the digital output.
•Active
In the active mode +24 V will be applied across
the output.
•Passive
In the passive mode the output of the applied
potential switches to ground.
Observe the maximum output current!
Maximum output current in case of internal voltage supply
via A1/+ and A2/-: 200 mA in total to X1.
Q
x
X1
X1
+
Q
x
X1
X1
10.1
1.10.4
Digital 2
Refer to
.
10.1
1.10.5
Buzzer
The following parameters can be set for the buzzer:
10.1
1.10.5.1
TEST
The functional test of the buzzer can be activated or deactivated. This only applies to the
manual test and not to the cyclic device self test:
10.1
1.10.5.2
Function 1
Refer to
.
10.1
1.10.5.3
Function 2
Refer to
.
10.1
1.10.5.4
Function 3
Refer to
.
•on
The manual test activates the buzzer sound.
•off
The manual test does not activate the buzzer
sound.