Commissioning
32
5.2
Switching on
1. Connect the supply voltage of all devices connected to the BMS bus.
Initially, the "ON" LED flashes on the EDS... and the EDS...-D graphic dis-
play shows the (BENDER) welcome screen. The "ON" LED then lights up
permanently.
2. Eliminate insulation and device errors. If a response value is exceeded
or device error messages occur, this is indicated on the EDS... by means
of the alarm LED lighting up and an associated message appearing on
the graphic display (EDS...-D only).
– You can find information about the alarms on the EDS...-D in the
"Alarm/Meas. values" menu. Information on the EDS...-L can be dis-
played via the BMS master.
– Eliminate the insulation faults detected by the EDS....
– The EDS...-D indicates any device errors that have occurred on its
display, the EDS...-L displays an error code.
– Device errors may be caused by measuring current transformers
not being connected. Check the measuring current transformer
connections. Disable transformer monitoring for measuring chan-
nels that are not required (refer to "chapter 6.6.3.2 Settings menu 2:
Channel", submenu "2.CT" on page 50).