![Bender B980853 Manual Download Page 17](http://html1.mh-extra.com/html/bender/b980853/b980853_manual_2731770017.webp)
Commissioning and continous operation
17
If the shutdown was carried out as intended:
1. Press the
combined
test/reset button "T/R“ for 1 s
– VG12 reconnects the socket-outlets (The hand lamp lights up).
– The alarm LEDs
"
AL1
"
and
"
AL2
"
go out.
2. Ensure that this manual as well as the instructions of the power generator are kept
within easy reach near the device.
5.3 Test before daily use
Check the safe function of the VG12 daily before each use of the power generator:
1. Start the power generator.
2. Plug a load (e.g. a hand lamp) into a socket-outlet of the VG12 safety distributor.
3. Press the
combined
test/reset button "T/R" of the VG12 for 3 s. A short time later, "tES"
appears on the display for a few seconds.
In the following, the alarm LEDs "AL1" and "AL2" light up and the VG12 disconnects all
poles of the safety socket-outlets. (The hand lamp goes out).
If the shutdown was carried out as intended:
1. Press the
combined
test/reset button "T/R“ for 1 s
– VG12 reconnects the socket-outlets (The hand lamp lights up).
– The alarm LEDs
"
AL1
"
and
"
AL2
"
go out.
2. After successful testing, the power generator can be used as normal.
CAUTION
Risk of malfunction!
If the power generator is
not
switched off after pressing the combined
test/reset button "T/R", a fault exists. Protect the power generator
against accidental switch-on. Please contact Bender.