Mounting, connection and commissioning
25
CP9xx_D00349_08_M_XXEN/02.2022
BMS
BCOM
The CP9xx alarm indicator and operator panel is to be operated as a
master
if
- Parameters are queried or changed
- Certain control commands are issued
Please note that not all BMS masters can surrender their master function!
Multiple assignment of addresses
The factory setting for the system name on all Bender BCOM devices is "SYSTEM".
If several systems with the same system name are integrated into the same net-
work, addresses are assigned twice. This leads to transmission errors. Always en-
ter a unique BCOM system name during initial configuration.