Parameter overview
26
isoGEN523_D00320_04_M_XXEN/06.2018
5.5 Function configuration
FAC
= Factory settings;
Cs
= Customer settings
5.6 Measured value description
Parame
ter
Activation
Setting value
Description
Available via
FAC
Cs
Value
range
FAC
Cs
BMS Modbus
GEn/dc
GEn/dc
GEn
Selection of the system to be
monitored
GEn
: Generators (AC, AC with
connected DC, DC )
dc
: DC system
X
X
nEt
on
Test of the system connection
during device test
X
X
S.Ct
on
Device test during device
start
X
X
FAC
Restore factory settings
X
X
SYS
For Bender Service only
Description
Insulation resistance
R
F
1 kΩ ... 2 MΩ Resolution 1 kΩ
System leakage capacitance
C
e
1
nF
... 17
μF
Resolution 1
nF
Nominal system voltage L1 - L2
U
n
0 V
trueRMS
… 500 V
trueRMS
Resolution 1 V
trueRMS
Residual voltage L1/+ - PE
U
L1e
0 V
DC
… ±500 V
DC
Resolution 1 V
DC
Residual voltage L2/-
- PE
U
L2e
0 V
DC
… ±500 V
DC
Resolution 1 V
DC
Fault location in %
-100 % …+100 %